CT-6500 Series 2 Operating Instructions
29
9.1.2 Timing an OPEN Operation with Insertion Resistors
The CT-6500 can time breakers with insertion resistors. The insertion resistor can
range from 10 to 7,000 Ohms. Any insertion resistor more than 7,000 Ohms is detected as
an open circuit. The timing results will show the main contact time and the insertion resistor
contact time. Graphic reports will show the main contact and the resistor contact activities
on each of the channels.
Table 4.0 Open Operation With Insertion Resistor
STEP
OPERATION
ACTION
DISPLAY
1
READY TIMER FOR BREAKER OPERATION.
PRESS #1 KEY.
INSERTION RESISTOR?
1.NO
2.YES
2
SELECT INSERTION RESISTOR.
PRESS #2 KEY.
RESISTOR VALUE:
1.LESS THAN 1000 OHM
2.1000 to 2000 OHM
3.MORE THAN 2000 OHM
3
SELECT LESS THAN 1000 OHM RESISTOR
RANGE.
PRESS #1 KEY.
TIMING WINDOWS:
1.WINDOW = 1 SEC
2.WINDOW = 10 SEC
3.WINDOW = 20 SEC
4
SELECT 1-SECOND WINDOW.
PRESS #1 KEY.
TRIGGER MODE:
1. Internal Trigger
2. External Trigger
5
SELECT INTERNAL TRIGGER.
PRESS #1 KEY.
TIMING MODE:
1. OPEN
2. CLOSE
3. O-C
4. C-O
5. O-C-O
6
SELECT OPEN OPERATION.
PRESS #1 KEY.
OPEN TIMING
Hold "ARM" Switch,
Then "START".
"STOP" to ABORT
7
INITIATE OPEN COMMAND.
HOLD THE "ARM"
SWITCH AND
PRESS THE "START"
KEY.
TEST IN PROGRESS
Hold "ARM" Until
Test complete.
(Up to 25 seconds)
8
ANALYZER IS READY TO OUTPUT RESULTS.
NONE.
1.RUN TEST 06/12/07
2.GET RSLT 19:20:01
3.SET-UP
4.DIAGNOSTIC
Go to section 9.2 to print a test report.
Содержание CT-6500 2 Series
Страница 22: ...CT 6500 Series 2 Operating Instructions 21 Figure 4 0 Series Contact Cable Connection...
Страница 77: ...CT 6500 Series 2 Operating Instructions 76 APPENDIX F SIEMENS TCP Breaker Velocity Calculation...
Страница 78: ...CT 6500 Series 2 Operating Instructions 77 APPENDIX G SIEMENS SPS2 Breaker Velocity Calculation...
Страница 79: ...CT 6500 Series 2 Operating Instructions 78 APPENDIX H CT 6500 SIEMENS SPS2 Test Plan...
Страница 82: ...www vanguard instruments com...