3.7 I

NSTALLING

2 E

XTERIOR

H

OODS

Choose an appropriate location to install the exterior
hoods:

• There must be a minimum distance of 6 feet (1.8 m) 

between the hoods to avoid cross-contamination

• There must be a minimum distance of 18 inches 

(457 mm) from the ground

Make sure the intake hood is at least 6 feet (1.8 m) away
from the following:

• Dryer exhaust, high efficiency furnace vent, central 

vacuum vent

• Gas meter exhaust, gas barbecue grill

• Any exhaust from a combustion source

• Garbage bin and any other sources of contamination

Refer to figure beside for connecting insulated ducts to the
exterior hoods. An “Anti-gust intake hood’’ should be
installed in regions where a lot of snow is expected to fall.

3. INSTALLATION 

(CONT’D)

VD002

8

T

APE AND DUCT TIE

O

PTIONAL

DUCT LOCATION

E

XHAUST HOOD

I

NTAKE HOOD

18’’

(457 

MM

)

18’’

(457 

MM

)

6’’ Ø

(152 

MM

)

18’’

(457 

MM

)

6’

(1.8 

M

)

6’

(1.8 

M

)

- 9 -

3.8 C

ONNECTING THE

D

RAIN

VO0010

From the inside of the unit, punch
both knock-out sections located at the
bottom of the unit.

If using a pail to
collect water,
locate the tube end
approximately 1”
from the top of
the pail in order
to prevent water
from being
drawn back up
into the unit.

VO000

3

In order to keep the drain pan intact,
hand tighten both plastic drain fittings
to the unit using the gaskets, washers
and nuts as shown.

Make a water trap loop in the tube to
prevent the unit from drawing
unpleasant odors from the drain
source. Make sure this loop is located
BELOW the “T” as shown. This will
prevent water from being drawn back
up into the unit in case of negative
pressure. Run the tube to the floor
drain or to an alternative drain pipe or
pail. Be sure there is a slight slope for
the run-off.

VO0005A

± 12" 

(± 

3

05 mm)

± 12" 

(± 

3

05 mm)

Cut 2 sections of the plastic tube,
about 12” (305 mm) long, and attach
them to each drain fitting. Join both
short sections to the “T” junction and
main tube as shown.

VO0011

T

IE WRAP

T

O DRAIN

VD02

3

1A

± 1

Содержание 90 H

Страница 1: ...ESIDENTIAL USE ONLY READ AND SAVE THESE INSTRUCTIONS 03451 rev C VB0110 These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US...

Страница 2: ...e an extension cord 7 Do not install in a cooking area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicin...

Страница 3: ...ACE 12 6 WIRING DIAGRAM 13 7 BALANCING THE UNIT 14 8 SERVICE PARTS 15 9 TROUBLESHOOTING 16 TABLE OF CONTENTS 3 1 TECHNICAL DATA 1 1 AIR DISTRIBUTION 1 2 DEFROST CYCLES NORMAL OPERATION DEFROST VF0022...

Страница 4: ...ion but we recommend it NOTE Home with multiple forced air systems should have one unit on each system Stale air coming from the registers located at the highest level of the house is exhausted to the...

Страница 5: ...hains and springs provided See illustrations beside VD0037 CAUTION Make sure the unit is level VD0038 3 3 PLANNING OF THE DUCTWORK Keep it simple Plan for a minimum of bends and joints Keep the length...

Страница 6: ...having a high speed performance of 222 cfm VI0003 END BRANCHES 5 70 CFM MAIN BRANCH 6 140 CFM VI0004 5 5 5 65 cfm 6 129 cfm 6 138 cfm 6 93 cfm 7 222 cfm 7 222 cfm 6 96 cfm 5 64 cfm 6 84 cfm 4 42 cfm...

Страница 7: ...s use approved tools and materials Respect all corresponding laws and safety regulations Please refer to your local building code CAUTION When performing duct connections to the furnace supply duct th...

Страница 8: ...m building port as shown below 3 6 CONNECTING THE DUCTS TO THE UNIT Insulated flexible ducts Use the following procedure for connecting the insulated flexible ducts to the ports of the unit Exhaust ai...

Страница 9: ...8 M 6 1 8 M 9 3 8 CONNECTING THE DRAIN VO0010 From the inside of the unit punch both knock out sections located at the bottom of the unit If using a pail to collect water locatethetubeend approximate...

Страница 10: ...nit is plugged after being unplugged or after a power failure the unit will perform a 30 second booting sequence before starting to operate During the booting sequence the integrated control LED will...

Страница 11: ...sure that the wires do not short circuit between themselves or by touching any other components on the wall control Avoid poor wiring connections To reduce electrical interference noise potential do n...

Страница 12: ...4 2 ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS CONT D 12 5 ELECTRICAL CONNECTION TO THE FURNACE For a furnace connected to a cooling system On some older thermostats energizing the R and G termin...

Страница 13: ...1 J2 2 J2 1 F1 J12 5 J12 4 J12 3 J2 3 J2 4 J2 5 Door interlock switch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10...

Страница 14: ...t the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections NOTE It is suggested to start with the exhaust air flow reading because the exhaust has...

Страница 15: ...NCING DOUBLE COLLAR PORT 2 02256 02256 8 DRAIN CONNECTOR KIT 1 03203 03203 9 SMALL BASIC FILTER 1 09300 09300 10 HEAT RECOVERY CORE 1 03311 03311 11 BASIC FILTER 2 02300 02300 12 BLOWER ASSEMBLY INCLU...

Страница 16: ...ol or push button Jump the OL and OC terminals If the work OR its indicator light may be defective unit switch to high speed remove the does not stay on Humidity Control or push button and test it rig...

Отзывы: