3. INSTALLATION 

(CONT’D)

3.4 C

ALCULATING

D

UCT SIZE

(

CONT

D

)

NOTE: Examples 3.4.1 and 3.4.2 use imperial units. The same calculation applies to metric units.

3.4.1

Example of calculation

Problem: 

My installation requires two exhaust registers (one for the kitchen, and the other for 

the bathroom). I will connect these registers to a main duct which will connect to the unit (high 
speed performance value of 140 cfm). What size of duct should I use for the main exhaust duct 
and for both end branches leading to the registers? (See figure beside.)

Solution:

Simplified method. (For a more detailed method of calculating duct size, refer to the 

ASHRAE or HRAI HANDBOOK.)

Main duct: Table on page 5 indicates for a 6” Ø duct: recommended air flow: 120 cfm, maximum 
air flow: 180 cfm. The 140 cfm high speed air flow is close enough to the recommended value 
(120) and far away enough from the maximum value (180). Therefore, a 6” Ø duct or larger is 
an appropriate choice for the main exhaust duct.

End branches: Each end branch will have to transport a 70 cfm air flow (140 divided by 2). Table on page 5 indicates for a 5” Ø 
duct: recommended air flow: 75 cfm; maximum air flow: 110 cfm. The high speed air flow of 70 cfm is close enough to the
recommended value (75) and far away enough from the maximum value (110). Therefore, a 5” Ø duct or larger is an appropriate
choice for both end branches.

NOTE: A 4” Ø duct would have been too small because the maximum acceptable value for a 4” Ø duct is 60 cfm.

3.4.2

Example of a design for a fully ducted system with a unit having a high speed performance of 222 cfm.

VI000

3

E

ND

BRANCHES

5” Ø,

70 

CFM

M

AIN BRANCH

6”Ø, 140 

CFM

VI0004

5”

5”

5” Ø 65 cfm

6” Ø 129 cfm

6” Ø 138 cfm

6” Ø 93 cfm

7” Ø 222 cfm

7” Ø 222 cfm

6” Ø 96 cfm

5” Ø 64 cfm

6” Ø

84 cfm

4” Ø

42 cfm

4” Ø 42 cfm

4”

4”

4”

6”

6”

6”

6”

7”

7”

4”

4”

3.5 I

NSTALLING THE

D

UCTWORK AND

R

EGISTERS

3.5.1  F

ULLY

D

UCTED

S

YSTEM

(

AS ILLUSTRATED IN

S

ECTION

2.1)

Stale air exhaust ductwork

• Install the stale air exhaust registers where the contaminants are produced: kitchen, living room, etc. Position the registers as far 

from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.

• If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.

• Install the registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.

• If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min (122 m/min), then 

the register type is too small. Replace with a larger one.

Fresh air distribution ductwork

• Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.

• Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.

• Install the registers either in the ceiling or high on the walls with air flow directed towards the ceiling. (The cooler air will then cross 

the upper part of the room and mix with room air, before descending to occupant’s level.)

• If a register must be floor installed, direct the airflow up the wall.

WARNING

Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace, a gas
water heater or a fireplace.

0

!

- 6 -

Содержание 90 H

Страница 1: ...ESIDENTIAL USE ONLY READ AND SAVE THESE INSTRUCTIONS 03451 rev C VB0110 These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US...

Страница 2: ...e an extension cord 7 Do not install in a cooking area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicin...

Страница 3: ...ACE 12 6 WIRING DIAGRAM 13 7 BALANCING THE UNIT 14 8 SERVICE PARTS 15 9 TROUBLESHOOTING 16 TABLE OF CONTENTS 3 1 TECHNICAL DATA 1 1 AIR DISTRIBUTION 1 2 DEFROST CYCLES NORMAL OPERATION DEFROST VF0022...

Страница 4: ...ion but we recommend it NOTE Home with multiple forced air systems should have one unit on each system Stale air coming from the registers located at the highest level of the house is exhausted to the...

Страница 5: ...hains and springs provided See illustrations beside VD0037 CAUTION Make sure the unit is level VD0038 3 3 PLANNING OF THE DUCTWORK Keep it simple Plan for a minimum of bends and joints Keep the length...

Страница 6: ...having a high speed performance of 222 cfm VI0003 END BRANCHES 5 70 CFM MAIN BRANCH 6 140 CFM VI0004 5 5 5 65 cfm 6 129 cfm 6 138 cfm 6 93 cfm 7 222 cfm 7 222 cfm 6 96 cfm 5 64 cfm 6 84 cfm 4 42 cfm...

Страница 7: ...s use approved tools and materials Respect all corresponding laws and safety regulations Please refer to your local building code CAUTION When performing duct connections to the furnace supply duct th...

Страница 8: ...m building port as shown below 3 6 CONNECTING THE DUCTS TO THE UNIT Insulated flexible ducts Use the following procedure for connecting the insulated flexible ducts to the ports of the unit Exhaust ai...

Страница 9: ...8 M 6 1 8 M 9 3 8 CONNECTING THE DRAIN VO0010 From the inside of the unit punch both knock out sections located at the bottom of the unit If using a pail to collect water locatethetubeend approximate...

Страница 10: ...nit is plugged after being unplugged or after a power failure the unit will perform a 30 second booting sequence before starting to operate During the booting sequence the integrated control LED will...

Страница 11: ...sure that the wires do not short circuit between themselves or by touching any other components on the wall control Avoid poor wiring connections To reduce electrical interference noise potential do n...

Страница 12: ...4 2 ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS CONT D 12 5 ELECTRICAL CONNECTION TO THE FURNACE For a furnace connected to a cooling system On some older thermostats energizing the R and G termin...

Страница 13: ...1 J2 2 J2 1 F1 J12 5 J12 4 J12 3 J2 3 J2 4 J2 5 Door interlock switch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10...

Страница 14: ...t the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections NOTE It is suggested to start with the exhaust air flow reading because the exhaust has...

Страница 15: ...NCING DOUBLE COLLAR PORT 2 02256 02256 8 DRAIN CONNECTOR KIT 1 03203 03203 9 SMALL BASIC FILTER 1 09300 09300 10 HEAT RECOVERY CORE 1 03311 03311 11 BASIC FILTER 2 02300 02300 12 BLOWER ASSEMBLY INCLU...

Страница 16: ...ol or push button Jump the OL and OC terminals If the work OR its indicator light may be defective unit switch to high speed remove the does not stay on Humidity Control or push button and test it rig...

Отзывы: