background image

- 5 -

3. INSTALLATION

3.1 I

NSPECT THE

C

ONTENT OF THE

B

OX

• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door latches, power cord, etc.

Remove the hardware kit from the unit. Inspect the interior of the unit for damage. Ensure that heat recovery core, core filters, insulation,
dampers, etc. are all intact.

3.2 L

OCATING THE

U

NIT

Choose an appropriate location for the unit.

Within an area of the house where the ambient temperature is between 10°C (50°F) and 50°C (122°F) (basement, furnace room, 
closet, etc.).

• Away from living areas (dining room, living room, bedroom), if possible

So as to provide easy access to the interior of the unit, for maintenance.

Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.

Away from hot chimneys and other fire hazards.

Allow for a power source (standard 3-prong grounding outlet).

Close to a drain. If no drain is close by, use a pail to collect run-off.

Hang the unit with the four chains and springs provided.
See illustrations beside.

VD00

3

7

CAUTION

Make sure the unit is level.

VD00

38

3.3 P

LANNING OF THE

D

UCTWORK

• Keep it simple. Plan for a minimum of bends and joints. 

• Keep the length of insulated ducts to a minimum.

• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would 

cause clogging of the filters and recovery module.

• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.

3.4 C

ALCULATING

D

UCT SIZE

Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values.
Avoid installing ducts that will have to carry air flows near the maximum values and never install a duct if its air flow exceeds
the maximum value.

D

UCT

D

IAMETER

R

ECOMMENDED

A

IR

F

LOW

M

AXIMUM

A

IR

F

LOW

4” Ø (102 

MM

)

40 

CFM

(19 

L

/

S OR

68 

M

³/

H

)

60 

CFM

(28 

L

/

S OR

102 

M

³/

H

)

5” Ø (127 

MM

)

75 

CFM

(35 

L

/

S OR

127 

M

³/

H

)

110 

CFM

(52 

L

/

S OR

187 

M

³/

H

)

6” Ø (152 

MM

)

120 

CFM

(57 

L

/

S OR

204 

M

³/

H

)

180 

CFM

(85 

L

/

S OR

306 

M

³/

H

)

7” Ø (178 

MM

)

185 

CFM

(87 

L

/

S OR

314 

M

³/

H

)

270 

CFM

(127 

L

/

S OR

459 

M

³/

H

)

8” Ø (203 

MM

)

260 

CFM

(123 

L

/

S OR

442 

M

³/

H

)

380 

CFM

(179 

L

/

S OR

645 

M

³/

H

)

Содержание 90 H

Страница 1: ...ESIDENTIAL USE ONLY READ AND SAVE THESE INSTRUCTIONS 03451 rev C VB0110 These products earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US...

Страница 2: ...e an extension cord 7 Do not install in a cooking area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicin...

Страница 3: ...ACE 12 6 WIRING DIAGRAM 13 7 BALANCING THE UNIT 14 8 SERVICE PARTS 15 9 TROUBLESHOOTING 16 TABLE OF CONTENTS 3 1 TECHNICAL DATA 1 1 AIR DISTRIBUTION 1 2 DEFROST CYCLES NORMAL OPERATION DEFROST VF0022...

Страница 4: ...ion but we recommend it NOTE Home with multiple forced air systems should have one unit on each system Stale air coming from the registers located at the highest level of the house is exhausted to the...

Страница 5: ...hains and springs provided See illustrations beside VD0037 CAUTION Make sure the unit is level VD0038 3 3 PLANNING OF THE DUCTWORK Keep it simple Plan for a minimum of bends and joints Keep the length...

Страница 6: ...having a high speed performance of 222 cfm VI0003 END BRANCHES 5 70 CFM MAIN BRANCH 6 140 CFM VI0004 5 5 5 65 cfm 6 129 cfm 6 138 cfm 6 93 cfm 7 222 cfm 7 222 cfm 6 96 cfm 5 64 cfm 6 84 cfm 4 42 cfm...

Страница 7: ...s use approved tools and materials Respect all corresponding laws and safety regulations Please refer to your local building code CAUTION When performing duct connections to the furnace supply duct th...

Страница 8: ...m building port as shown below 3 6 CONNECTING THE DUCTS TO THE UNIT Insulated flexible ducts Use the following procedure for connecting the insulated flexible ducts to the ports of the unit Exhaust ai...

Страница 9: ...8 M 6 1 8 M 9 3 8 CONNECTING THE DRAIN VO0010 From the inside of the unit punch both knock out sections located at the bottom of the unit If using a pail to collect water locatethetubeend approximate...

Страница 10: ...nit is plugged after being unplugged or after a power failure the unit will perform a 30 second booting sequence before starting to operate During the booting sequence the integrated control LED will...

Страница 11: ...sure that the wires do not short circuit between themselves or by touching any other components on the wall control Avoid poor wiring connections To reduce electrical interference noise potential do n...

Страница 12: ...4 2 ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS CONT D 12 5 ELECTRICAL CONNECTION TO THE FURNACE For a furnace connected to a cooling system On some older thermostats energizing the R and G termin...

Страница 13: ...1 J2 2 J2 1 F1 J12 5 J12 4 J12 3 J2 3 J2 4 J2 5 Door interlock switch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10...

Страница 14: ...t the tubes to their appropriate high low fittings If the gauge drops below zero reverse the tubing connections NOTE It is suggested to start with the exhaust air flow reading because the exhaust has...

Страница 15: ...NCING DOUBLE COLLAR PORT 2 02256 02256 8 DRAIN CONNECTOR KIT 1 03203 03203 9 SMALL BASIC FILTER 1 09300 09300 10 HEAT RECOVERY CORE 1 03311 03311 11 BASIC FILTER 2 02300 02300 12 BLOWER ASSEMBLY INCLU...

Страница 16: ...ol or push button Jump the OL and OC terminals If the work OR its indicator light may be defective unit switch to high speed remove the does not stay on Humidity Control or push button and test it rig...

Отзывы: