- 5 -
3. INSTALLATION
3.1 I
NSPECT THE
C
ONTENT OF THE
B
OX
• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door latches, power cord, etc.
•
Remove the hardware kit from the unit. Inspect the interior of the unit for damage. Ensure that heat recovery core, core filters, insulation,
dampers, etc. are all intact.
3.2 L
OCATING THE
U
NIT
Choose an appropriate location for the unit.
•
Within an area of the house where the ambient temperature is between 10°C (50°F) and 50°C (122°F) (basement, furnace room,
closet, etc.).
• Away from living areas (dining room, living room, bedroom), if possible
•
So as to provide easy access to the interior of the unit, for maintenance.
•
Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
•
Away from hot chimneys and other fire hazards.
•
Allow for a power source (standard 3-prong grounding outlet).
•
Close to a drain. If no drain is close by, use a pail to collect run-off.
Hang the unit with the four chains and springs provided.
See illustrations beside.
VD00
3
7
CAUTION
Make sure the unit is level.
VD00
38
3.3 P
LANNING OF THE
D
UCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to a minimum.
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would
cause clogging of the filters and recovery module.
• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
3.4 C
ALCULATING
D
UCT SIZE
Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values.
Avoid installing ducts that will have to carry air flows near the maximum values and never install a duct if its air flow exceeds
the maximum value.
D
UCT
D
IAMETER
R
ECOMMENDED
A
IR
F
LOW
M
AXIMUM
A
IR
F
LOW
4” Ø (102
MM
)
40
CFM
(19
L
/
S OR
68
M
³/
H
)
60
CFM
(28
L
/
S OR
102
M
³/
H
)
5” Ø (127
MM
)
75
CFM
(35
L
/
S OR
127
M
³/
H
)
110
CFM
(52
L
/
S OR
187
M
³/
H
)
6” Ø (152
MM
)
120
CFM
(57
L
/
S OR
204
M
³/
H
)
180
CFM
(85
L
/
S OR
306
M
³/
H
)
7” Ø (178
MM
)
185
CFM
(87
L
/
S OR
314
M
³/
H
)
270
CFM
(127
L
/
S OR
459
M
³/
H
)
8” Ø (203
MM
)
260
CFM
(123
L
/
S OR
442
M
³/
H
)
380
CFM
(179
L
/
S OR
645
M
³/
H
)