RS−P Solar Water Pump Controller User Manual
22
Chapter 4 Routine Repair and Maintenance
Chapter 4 Routine Repair and Maintenance
The application environment (such as temperature, humidity, dust and powder, wool, smoke and
oscillation), burning and wearing of internal devices and other factors may increase the possibilities of
controller failure. To reduce the failures and prolong the service life the controller, it is necessary to
conduct routine repair and periodic maintenance.
Note:
1. Only the personnel receiving professional training can dismantle and replace the controller
components.
2. Prior to inspection and maintenance, please make sure that the power supply to the controller has
been disconnected for at least ten minutes or the CHARGER indictor is OFF, or there may be risks of
electric shock (the controller with power level of RS-P-4T11G/15L or above has CHARGER indicator).
3. Do not leave metal components and parts in the controller, or it may damage the controller.
4.1 Routine Maintenance
The controller shall be used under the allowable conditions as recommended in this manual and its
routine maintenance shall be conducted as per the table below.
Item
Inspection Contents
Inspection Means
Criteria
Operating
Environment
Temperature
Thermometer
-10 ~ +40
º
C
Derated at 40 to 50
º
C, and the rated output current shall be
decreased by 1% for every temperature rise of 1
º
C.
Humidity
Humidiometer
5 ~ 95%, no condensing
Dust, oil, water and drop Visual check
There are no dust, oil, water and drop.
Vibration
Special test instrument
3.5m/s2, 2~ 9Hz;
10m/s2,9~ 200Hz; 15m/s2,200~ 500Hz
Gas
Special test instrument,
smell check and visual
check
There are no abnormal smell and smoke.
controller
Overheat
Special test instrument
Exhaust normal
Noise
Listen
There is no abnormal noise.
Gas
Smell and visual check
There are no abnormal smell and smoke.
Physical appearance
Visual check
The physical appearance is kept intact.
Heatsink fan ventilation Visual check
There are no fouling and wool that block the air duct.
Input current
Amperemeter
In the allowable operating range. Refer to the nameplate.
Input voltage
Voltmeter
In the allowable operating range. Refer to the nameplate.
Output current
Amperemeter
In the rated value range. It can be overloaded for a short
while.
Output voltage
Voltmeter
In the rated value range.
Motor
Overheat
Special test instrument
and smell.
There are no overheat fault and burning smell.
Noise
Listen
There is no abnormal noise.
Vibration
Special test instrument
There is no abnormal oscillation.