Vacon 100 Flow
page
12
3.6 Quick setup parameter group
In addition to the Startup Wizard, the Vacon 100 has a quick setup menu for the most basic
parameters.
By changing a setting in the quick setup parameter group, this setting will also be changed
in the corresponding parameter group.
code
Parameter
Min
Max
ID
M1.1
Wizards
Starting various wizards
P1.2
Application
212
Standard
HVAC
PID control
Multi-pump (single drive)
Multi-pump (multi-drive)
P1.3
Minimum frequency
0
50
Hz
101
P1.4
Maximum frequency
20
320
Hz
102
P1.5
Acceleration time 1
0.1
3,000
s
103
P1.6
Deceleration time 1
0.1
3,000
s
104
P1.7
Current limit
3
variable
A
107
P1.8
Motor type
PM
Induction
PM motor (permanent magnet)
Induction motor
P1.9
Rated motor voltage
180
690
V
110
P1.10 Rated motor frequency 0
320
Hz
111
P1.11 Rated motor speed
0
62,500
RPM
112
P1.12 Rated motor current
0
variable
A
113
P1.13 Motor Cos phi
0
1
120
P1.14 Energy optimisation
enable
disable
666
P1.15 Identification
631
No action
At standstill
With the motor running
P1.16 Start function
505
Running start
Ramping
P1.17 Stop function
506
Ramping
Freewheel
P1.18 Automatic reset
enable
disable
731
P1.19 External error
701
No action
Alarm
Error
Error, freewheel
P1.20 Error AI too low
700
No action
Alarm
Alarm fixed frequency
Alarm last frequency
Error
Error, freewheel
P1.21
Remote operating
location
Fieldbus
I/O
terminal
172
P1.22 Reference selection I/O
117
For options, see manual
P1.23 Control panel selection
121
For options, see manual
P1.24
Fieldbus reference
selection
122
For options, see manual
P1.25 AI 1 signal range
0 to 10 V
0 to 20 mA
2 to 10 V
4 to 20 mA
379
P1.26 AI 2 signal range
0 to 10 V
0 to 20 mA
2 to 10 V
4 to 20 mA
390
P1.27 RO1 function
11001
For options, see manual
P1.28 RO2 function
11004
For options, see manual
P1.29 RO3 function
11007
For options, see manual
P1.30 AO1 function
10050
For options, see manual
The following parameters may differ, depending on the choice of the application.
P1.31. ...
for Standard and HVAC
P1.32. ...
for PID control
P1.33. ...
for multitopump (single drive)
P1.34. ...