Vacon 100 Flow
page
38
Parameter group
Description
Setting
P3.15.2
Number of pumps
1 to 8
P3.15.3
Pump ID number
1 to 8
P3.15.4
Start and feedback
Signals connected/Only start signal /
Not connected
P3.15.5
Pump block
Not used/Release
P3.15.6
Autochange mode
Blocked
Enabled (interval)
Enabled (weekdays)
P3.15.7
Autochange pumps
Auxiliary pumps/all pumps
P3.15.8
Autochange interval
0 to 3,000 h
P3.15.9
Autochange days
Sunday to Saturday
P3.15.10
Autochange time
00:00:00 to 23:59:59
P3.15.11
Autochange frequency limit
50 Hz.
P3.15.12
Autochange pump limit
Max. number of pumps
P3.15.13
Range
2% determined when pumps are switched on
P3.15.14
Range delay
5 s
P3.15.15
Constant production speed
100%
*) For the correct adjustment of the minimum frequency and sleep frequency, see Section 7.2
All these parameters are adjusted via the Wizard
The 4 to 20 mA pressure transducer is connected to AI 2, to the 4 (-) and 12 (+)
terminals
A through-connection must be made between 5 and 7.
Make sure that dipswitch AI 2 is in the Current signal position (down).
At the first and last connected regulators, make sure that the RS-485 bus termination
dipswitches are set to ON: all others should be set to OFF
Location and selection AI 2 dip switch and RS-485 bus termination
PID control is started by connecting 8 (DI 1) to 6 (+24 V).
Flushing is activated by connecting 9 (DI 2) to 6 (+24 V).
To switch from target value 1 to 2, connect 10 (DI 3) with
6 (+24 V).
A fault can be reset remotely by connecting 14 (DI 4) with 12 (+24 V).
Water thermostat (°C) or float must be connected to 16 (DI 6) and
12 (+24 V).
Connect A and B (RS-485) of the various regulators with each other.
For wiring diagrams, consult:
www.vanderendegroep.nl/nl/producten/frequentieregelaars/vacon-100-flow