6 Applications
6.1 Application defaults
The default values for each selected application are shown by in the table below.
Code
Parameter
Default setting
ID
Description
Sta
nd
ard
H
VAC
PID
co
ntro
l
Mu
lti
-p
ump
(s
ing
le
d
riv
e)
Mu
lti
-p
ump
(multi
-d
riv
e)
P3.2.1
Remote operating location
0
0
0
0
0
172
0 = Control I/O
P3.2.2
Local/Distance
0
0
0
0
0
211
0 = Remote
P3.2.6
Logic I/O A
2
2
2
2
2
300
2 = Forward-Reverse (Pulse)
P3.2.7
Logic I/OB
2
2
2
2
2
363
2 = Forward-Reverse (Pulse)
P3.3.1.5
Reference Selection I/O A
6
6
7
7
7
117
6 = AI 1 + AI 2
7 = PID
P3.3.1.6
Selection I/O reference B
4
4
4
4
4
131
4 = AI 1
P3.3.6.2
Flushing reference
0 Hz
0 Hz
0 Hz
0 Hz
50 Hz 1239
P3.5.1.1
Control signal 1 A
A.1
A.1
A.1
A.1
A.1
403
P3.5.1.2
Control signal 2 A
A.2
A.2
0.1
0.1
0.1
404
P3.5.1.4
Control signal 1 A
0.1
0.1
A.4
A.2
0.1
423
P3.5.1.7
Force control to I/O B
0.1
0.1
A.6
A.3
0.1
425
P3.5.1.8
Force I/O B-reference
0.1
0.1
A.6
A.3
0.1
343
P3.5.1.11
Close external error
A.3
A.3
A.2
0.1
A.6
405
P3.5.1.13
Close error reset
A.6
A.6
A.3
0.1
A.4
414
P3.5.1.21
Fixed frequency selection 0
A.4
A.4
A.5
0.1
0.1
419
P3.5.1.22
Fixed frequency selection 1
A.5
A.5
0.1
0.1
0.1
420
P3.5.1.31
PID SP selection
0.1
0.1
0.1
0.1
A.3
1047
P3.5.1.36
Activation flushing reference 0.1
0.1
0.1
0.1
A.2
530
P3.5.1.42
Pump 1 block
0.1
0.1
0.1
A.4
0.1
426
P3.5.1.43
Pump 2 block
0.1
0.1
0.1
A.5
0.1
427
P3.5.1.44
Pump 3 block
0.1
0.1
0.1
A.6
0.1
428
P3.5.3.2.1
RO1 function
2
2
2
49
2
11001
2 = In operation
49 = Multi-pump K1 control
P3.5.3.2.4
RO2 function
3
3
3
50
3
11004
3 = Error
50 = Multi-pump K2 control
P3.5.3.2.7
RO3 function
1
1
1
51
1
11007
1 = Ready
51 = Multi-pump K3 control
P3.13.2.6
Reference point source 1
select
-
-
3
3
3
332
3 = AI 1
P3.13.2.10
Reference point source 2
select
-
-
-
-
1
431
1 = Control panel ref. point 1
P3.13.3.1
PID feedback function
-
-
1
1
1
333
1 = Only source 1 in use
P3.13.3.3
PID feedback source
-
-
2
2
2
334
2 = AI 2
P3.15.1
Multi-pump, mode
-
-
-
0
2
1785
0 = Single drive
2 = Multi-master
P3.15.2
Number of pumps
1
1
1
3
3
1001
P3.15.5
Pump block
-
-
-
1
1
1032
1 = Unblocked
P3.15.6
Autochange
-
-
-
1
1
1027
1 = enabled
P3.15.7
Autochange pumps
-
-
-
1
1
1028
1 = All pumps
P3.15.8
Autochange interval
-
-
-
48 h
48 h
1029
P3.15.11
Autochange frequency limit
-
-
-
25 Hz 50 Hz 1031
P3.15.12
Autochange pump limit
-
-
-
1
3
1030
P3.15.13
Range
-
-
-
10%
10%
1097
P3.15.14
Range delay
-
-
-
10 s
10 s
1098
P3.15.15
Constant production speed
-
-
-
-
100% 1513
6.2 Start Application via Wizard