Technical description
5 Control functions
5.7 Controllable objects
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
149
5.7.1.
Local/Remote selection
In Local mode, the output relays can be controlled via a local
HMI, but they cannot be controlled via a remote serial
communication interface.
In Remote mode, the output relays cannot be controlled via a
local HMI, but they can be controlled via a remote serial
communication interface.
The selection of the Local/Remote mode is done by using a local
HMI, or via one selectable digital input. The digital input is
normally used to change a whole station to a local or remote
mode. The selection of the L/R digital input is done in the
“Objects” menu of the VAMPSET software.
NOTE! A password is not required for a remote control operation.