Technical description
2 Protection functions
2.21 Programmable stages (99)
VM50.EN004
VAMP 24h support phone +358 (0)20 753 3264
93
Parameters of the programmable stages PrgN (99)
Parameter Value
Unit Description
Note
Status -
Blocked
Start
Trip
Current status of the stage
F
F
SCntr
Cumulative
start
counter C
TCntr
Cumulative trip counter
C
SetGrp
1 or 2
Active setting group
Set
SGrpDI
-
DIx
VIx
LEDx
VOx
Digital signal to select the
active setting group
None
Digital input
Virtual input
LED indicator signal
Virtual output
Set
Force Off
On
Force flag for status forcing
for test purposes. This is a
common flag for all stages and
output relays, too.
Automatically reset by a 5-
minute timeout.
Set
Link
(See
Name for the supervised
signal
Set
(See Table
Value of the supervised signal
Cmp
>
<
Mode
of
comparison
Over protection
Under protection
Set
Pickup
Pick up value scaled to
primary level
Pickup
pu
Pick up setting in pu
Set
t
s
Definite operation time.
Set
Hyster
%
Dead band setting
Set
NoCmp
pu
Minimum value to start under
comparison. (Mode='<')
Set
Set = An editable parameter (password needed)
C = Can be cleared to zero
F = Editable when force flag is on
Recorded values of the latest eight faults
There is detailed information available of the eight latest
faults: Time stamp, fault value and elapsed delay.