Technical description
2 Protection functions
2.12 Directional earth fault protection
I0
φ
> (67N)
VM50.EN004
VAMP 24h support phone +358 (0)20 753 3264
67
Parameter Value
Unit Description
Note
Io
>
A
Pick-up value scaled to
primary value
Io
>
pu
Pick-up setting relative to the
parameter “Input” and the
corresponding CT value
Set
Uo>
%
Pick-up setting for U
0
Set
Uo %
Measured
U
0
Curve
DT
IEC
IEEE
IEEE2
RI
PrgN
Delay
curve
family:
Definite time
Inverse time. See chapter
Set
Type
DT
NI
VI
EI
LTI
Paramet
ers
Delay type.
Definite time
Inverse time. See chapter
Set
t> s
Definite operation time (for
definite time only)
Set
k>
Inverse delay multiplier (for
inverse time only)
Set
Mode ResCap
Sector
Undir
High impedance earthed nets
Low impedance earthed nets
Undirectional mode
Set
Offset
Angle offset (MTA) for RecCap
and Sector modes
Set
Sector
Default
= 88
±°
Half sector size of the trip
area on both sides of the offset
angle
Set
ChCtrl
Res
Cap
DI1, DI2
VI1..4
Res/Cap control in mode
ResCap
Fixed to Resistive
characteristic
Fixed to Capacitive
characteristic
Controlled by digital input
Controlled by virtual input
Set
InUse
-
Res
Cap
Selected submode in mode
ResCap.
Mode is not ResCap
Submode = resistive
Submode = capacitive