background image

 

 

Page 17 

Complete Assembly  

 

26) Remove the end cap and insert the body gasket/seal.  

 

27) Recheck/re-inspect the sealing faces on ball, body and end cap to ensure they were not damaged 
during handling. 

 

28) Replace all damaged body studs. Apply Copper-Based Anti-Seize Grease high temperature com-
pound to the threads. 

CAUTION!  Never turn a nut more than ¼ 
turn with out moving to a different body nut.

 

NOTE:

 THE STAR PATTERN IS EXTREMELY IMPORTANT.

 

33) Cycle the valve manually to verify that it is functioning correctly.  

 

34) Re-torque the packing gland bolts evenly to the values given in Table 2.  

32) During the entire initial pull-down the two faces should re-
main precisely parallel. Failure to do so may result in a faulty 
seal. Torque in a star pattern to 1/3 of torque value listed in 
Table 1. Then torque in a star pattern to 2/3 of torque value 
listed in Table 1. Then repeat again at the full torque value of 
Table 1. For valves larger than 10 inches, repeat the last 
torque values (full torque). 

31) Tighten the body studs/nuts evenly, observing the body gasket 
pull-down. Using gradually increasing torque levels, tighten oppo-
site bolts using a 

star-like pattern

 until the body and end cap are 

pulled face-to face

.

 

30) Insert the 

new

 ValvTechnolo-

gies body seal or gasket into the 
body, being certain that the top 
surface is precisely parallel with 
the body face.  

29) Replace Belleville spring, 
upstream seat and ball. 

 

Ensure the mate lapped side 
is facing the end cap in the 
valve body. 

Содержание V1 Series

Страница 1: ...Page VALVTECHNOLOGIES INC BALL VALVE Installation and Operations Maintenance Manual...

Страница 2: ...8 LUBRICATION 8 TORQUE TABLES 8 STEM ROTATION POSITION 9 ACTUATORS 9 IV MAINTENANCE 9 DISASSEMBLY 9 REPAIR REWORK 10 11 BELLVILLE SPRING HEIGHTS 11 12 RE ASSEMBLY 12 13 INSTALLING ACTUATOR 13 PRESSURE...

Страница 3: ...l is to describe procedures that will ensure safe and successful installation operation and maintenance of the metal seated ball valve assuming a trouble free service life Difficulties encountered in...

Страница 4: ...oad Belleville Spring Upstream Seat Guide Body Seal Hard coated Integral Seat Hard coated Ball High Load Belleville Spring Actuator Mounting Pad Live Loaded Gland Springs Gland Gland Packing Actuator...

Страница 5: ...ecial Port ACTUATION Lever Operated LV Cast 150 600 Forged 900 Up LC Cast 900 Up LF Forged 150 600 Bare Stem BS Cast 150 600 Forged 900 Up BC Cast 900 Up BF Forged 150 600 VALVE SIZE Nominal Valve Siz...

Страница 6: ...h electric actuators should be cycled to the mid stroke position before cycling under power WARNING VALVES SHOULD NEVER BE USED AS A STRUCTURAL MEMBER ORIENTATION CAUTION Valves must be installed with...

Страница 7: ...t insulating or stress relieving technique may damage the valve and void the warranty CAUTION Valve must be OPEN during welding CAUTION Valve insulation is prohibited during stress relieving Only insu...

Страница 8: ...9 210 285 1 3 8 35 950 1288 290 393 1 1 2 38 1250 1695 370 502 1 5 8 41 1600 2169 480 651 1 3 4 44 2060 2793 500 678 1 7 8 48 2500 3390 750 1017 2 51 3000 4067 900 1220 3 76 10300 13965 3100 4203 3 1...

Страница 9: ...actuators should be inspected every three months and be replenished or replaced if required On actuated and gear operated valves an arrow shows the valve position The stem gland and ball and in some...

Страница 10: ...iding excessive force remove the entire actuator assembly 6 Remove body seal or gasket depending upon valve design 7 Remove body gasket if applicable 8 Remove ball after mark ing orientation and prote...

Страница 11: ...e Ranges Other Valve Components In general these may be cleaned and returned to service If rework is required consult ValvTechnologies Engineering Department The ball is lapped to the end cap using 3...

Страница 12: ...ats are parallel to bore 2 Stem shall be inserted through the stem hole from the body cavity side NOTE Mark on top of stem should be on the left of the valve when looking down on the stem and facing d...

Страница 13: ...After tightening the bolts the concentricity should again be checked Any misalignment of the operator to the valve may cause binding in the operator which may cause damage to either the valve or the o...

Страница 14: ...4 068 1 727 1 1 2 38 045 1 143 068 1 727 2 1 8 54 048 1 219 071 1 803 3 1 16 78 078 1 981 105 2 667 4 1 16 103 095 2 413 125 3 175 5 1 8 130 120 3 048 145 3 683 6 1 16 154 145 3 683 178 4 521 8 1 16 2...

Страница 15: ...ecause of access use alternative method shown to the left Belleville Spring Standoff 19 Measure Belleville Spring height Refer to Table 3 for acceptable height range If height is out of specification...

Страница 16: ...m SEAT BALL GAP in mm MINIMUM MAXIMUM 5 8 16 N A 087 2 210 1 1 8 29 N A 075 1 905 1 1 2 38 032 813 046 1 168 2 1 8 150 300 54 N A N A 2 1 8 600 4500 54 040 1 016 056 1 422 3 1 16 78 053 1 346 067 1 70...

Страница 17: ...s should re main precisely parallel Failure to do so may result in a faulty seal Torque in a star pattern to 1 3 of torque value listed in Table 1 Then torque in a star pattern to 2 3 of torque value...

Страница 18: ...will not rotate or operate 1 Actuator has failed 2 Valve packed with debris 3 Stem key has sheared 4 Ball seat gap incorrect 1 Replace or repair actuator 2 Cycle flush valve to re move debris 3 Deter...

Страница 19: ...es below RECOMMENDED SPARE PARTS FOR V1 SERIES BALL VALVES CLASS PART DESCRIPTION QTY SAME TYPE SIZE PERCENT COVERAGE A Gland Packing Gland Load Springs 1 3 70 B Body Gasket Metal Belleville Spring 1...

Страница 20: ...5 TEXAS ValvTechnologies Inc 5904 Bingle Road Houston Texas 77092 U S A Telephone 713 860 0400 Facsimile 713 860 0499 E mail sales valv com Web www valv com Celtex Industries White Oak Texas 903 297 8...

Отзывы: