3.4.

FITTING THE CLOSURE PLATE 

(Figures 4 & 5)

3.4.1.

If a centre gas pipe connection is required
cut an opening at the bottom of the closure
plate. (The gap between the pipe and the
opening in the closure plate should be
sealed with tape after connection,)

3.4.2.

Hearth mounting 

(figure 5)

The closure plate must be fitted and sealed
to the hearth and fireplace opening using a
suitable heat resistant material. If necessary
cut the closure plate. Leave the closure plate
sufficiently large to overlap the fireplace
opening by 25mm. Make sure that the
rectangular air relief openings are fully
within the fireplace opening.

3.4.3

Wall mounting 

(Figure 6)

The closure plate must be fitted and sealed
to the fireplace opening using a suitable heat

resistant material. If necessary cut the
closure plate. Leave the closure plate
sufficiently large to overlap the fireplace
opening by 25mm. Make sure that the
rectangular air relief openings are fully
within the fireplace opening.
The bottom of the fire must be at least
102mm above any carpet or other floor
covering. To achieve this, the bottom of the
closure plate  must also be at least 102mm
above the finished floor covering. The centre
of the flue spigot hole will be at least 486mm
above the finished floor covering.
1. To improve appearance, remove the
front adjustment screws from the bottom
bar of the fire.
2. Place the closure plate over the fireplace
opening in its proper position.
3. Mark the positions of the four wall fixing
holes. Use only the lower of the top two
pairs of holes.
4. Remove the plate. Drill and plug the wall
using no. 10 wall plugs.
5. Put the closure plate back in position.
Make sure that the holes line up with the
wall plugs. Seal the plate to the wall with
suitable heat resistant tape. 

3.4.4.

Check the flue pull with closure plate fitted
by applying a lighted match or smoke match
to the flue spigot opening in the closure
plate and observe the smoke. If there is a
definite flow continue with the installation. If
not check the fitting of the closure plate. The
fireplace flue pull check described in section
3.2 should have confirmed that the fireplace
itself is satisfactory.

Page 8

INSTALLATION & SERVICING INSTRUCTIONS

figure 4

figure 5

figure 6

Valor Folium Format U/down 12/4  5/22/00  9:33 AM  Page 8

Содержание regency 328

Страница 1: ...IRELAND IE ONLY We trust that these instructions give sufficient details to enable this appliance to be installed and maintained satisfactorily However if further information is required our Valor adv...

Страница 2: ...ndards of safety quality and performance Careful Installation Valor is a Corgi registered company All our gas fires must be installed by a competent Corgi Registered Installer in accordance with our I...

Страница 3: ...ting the radiants 9 Full operating checks 9 Control setting check 9 Fitting bottom panel trims 10 Spillage check 10 Fitting dress guard 11 Final review 11 Servicing parts replacement 11 Replacing radi...

Страница 4: ...ers to work to recognised standards In the United Kingdom the installation must also be in accordance with A These instructions B All the relevant parts of local regulations C The current edition of t...

Страница 5: ...system conforming to BS1289 The appliance is suitable for installations conforming to older versions of BS1289 as well as the current edition The flue blocks must have a minimum width not less than 63...

Страница 6: ...bottom of the flue spigot See figure 2 2 7 The front face of the fireplace should be reasonably flat to ensure that a good seal can be made with the closure plate 2 8 The minimum clearance from the to...

Страница 7: ...ting to install it is worth checking that the piezo electric spark ignition system operates satisfactorily To initiate the spark depress the control knob and while keeping it depressed turn to the 1 I...

Страница 8: ...ther floor covering To achieve this the bottom of the closure plate must also be at least 102mm above the finished floor covering The centre of the flue spigot hole will be at least 486mm above the fi...

Страница 9: ...safety and servicing 4 3 3 The supply pipe must be of a rigid material e g copper A flexible connection must not be made 4 3 4 Pressure check the installation pipework for gas soundness in accordance...

Страница 10: ...nd tighten their securing screws 5 3 SPILLAGE CHECK A spillage check must be made before leaving the installed appliance with the customer 5 3 1 Close all doors and windows in the room containing the...

Страница 11: ...the radiants 6 6 Advise that any cleaning must only be carried out when the fire is off and cold 6 7 Mention that the radiants may become brown with use that this is quite normal and has no adverse e...

Страница 12: ...cage is cleaned before refitting Make sure that it locates squarely onto the pilot unit without any gaps between the cage edges and the pilot unit 7 4 TO REMOVE THE BURNER GAS TAP PILOT ASSEMBLY 7 4...

Страница 13: ...ing the split pin 7 8 TO REMOVE THE COMPLETE FIRE TO CHECK CHIMNEY FOR DEBRIS 7 8 1 To gain access see section 7 2 7 8 2 Remove the radiants and store in a safe place 7 8 3 Remove the floor plate 7 8...

Страница 14: ...levels of personal safety and performance efficiency it is essential that the opening at the back of the fire and the flue are kept clear of any form of obstruction It is possible that deposits of mo...

Страница 15: ...leaned with a damp cloth and dried with a soft duster Obstinate marks can be removed from the guard and trims using soapy water Never use abrasive cleaners The radiants can be cleaned with a soft brus...

Страница 16: ...pilot The pilot flame can be seen through the opening immediately below the centre radiant Figure 2 If the pilot does not light turn the control knob to OFF and try again In the unlikely event of fai...

Страница 17: ...will automatically shut off the supply of gas to the fire if for any reason the pilot goes out If this device does operate or if the fire is turned off accidentally or intentionally always wait three...

Страница 18: ...IN THE UNITED KINGDOM GB AND THE REPUBLIC OF IRELAND IE ONLY We trust that these instructions give sufficient details to enable this appliance to be installed and maintained satisfactorily However if...

Страница 19: ...ndards of safety quality and performance Careful Installation Valor is a Corgi registered company All our gas fires must be installed by a competent Corgi Registered Installer in accordance with our I...

Страница 20: ...you care for your Valor gas fire Please read thoroughly before using and keep for future reference We trust that these instructions give sufficient details to enable this appliance to be operated and...

Отзывы: