INSTALLER’S GUIDE
Page 22
Figure 18. Upper Cable
Retention
Figure 17. Eyebolt Positions
8.2
Method 2 - Cable
Retention and Floor Fixing.
1.
Make sure that the relevant areas
at the fireplace back or floor are
sound enough to take the eyebolts
and screws. If these areas have
deteriorated due to prolonged use
they should be made sound with a
suitable cement.
2.
Drill four holes in the rear wall
or floor of the fireplace for the
eyebolt plugs. The holes should be
drilled within the range of positions
shown in figure 17 using a no.12
masonry drill. The holes should be
equidistant each side of the centre
line of the fireplace to ensure that
the appliance finishes centrally in
the opening when tension is applied
to the cables.
3.
Insert a fibre plug into each
hole. Use the fibre plugs supplied
with this appliance -
Never use
plastic plugs instead of the fibre
plugs supplied
.
Screw the eyebolts into the plugs.
Make sure that the bolts are secure.
4.
Place the convection box unit close to the
fireplace but allow sufficient access into the
fireplace opening so that the cables can be threaded
through the eyebolts and returned through the back
of the convection box. If a concealed connection is
being used, insert the convection box into the
fireplace feeding the supply pipe through the pierced
hole in the rear grommet.
5.
The convection box has two holes at each side of
the convected air opening. Insert one end of each cable (one cable each side) from the
back through the lower of the two holes and return the end through the upper of the
holes. See figure 18. Give the cables a pull so that they grip against the convection box
flanges.