Gas Supply

Only persons licensed to work with gas piping may make the necessary gas connection to this appliance. 

You are now ready to hook up the gas supply. Be sure that gas plumbing instructions and all provincial and local 
codes are carefully followed. Use approved 

fl

 exible gas connections or rigid piping, depending on provincial 

and local codes, to attach burner to gas supply. Be sure to use proper size gas supply line. Carefully check all 
connections for gas leaks with soap and water solution.
Each installation must conform to all local, provincial and national codes. Refer to the national fuel gas code, local 
zoning and code authorities for details on installation requirements.

11.1 Existing Gas Supply

Before interrupting the existing gas supply it is recommended that the following be checked:

Shut down all gas appliances and carry out a pressure test to insure there are no existing leaks on the system.
Before connecting the appliance to the gas supply line, double-check that the appliance you have purchased is designed 
for the gas type you are using. The gas type markings are located on the certi

fi

 cation label and also on the appliance’s gas 

valve.
Check the gas pressure to insure you will be able to supply the minimum inlet pressure for the appliance.
Check your pipe sizing to insure that suf

fi

 cient volume will be supplied to the appliance.

11.2 Gas Supply Installation

Provide adequate clearance for proper installation and checking of the gas connections.
Have your gas supplier or a quali

fi

 ed gas 

fi

 tter run a gas supply line into the gas 

fi

 replace. The line must be properly sized 

and 

fi

 tted according to the installation codes. Upstream of the appliance supply connection, the 

fi

 tter shall provide an easily 

accessible manual shut-off valve.
The gas supply pipe should enter the appliance case through the opening at the rear left side. The supply pipe should be 
connected to the appliance gas inlet pipe situated at the left side of the control unit. Supply line connection to the inlet pipe is 
3/8 NPT.
If the circulating fan is to be installed, be aware that the supply pipe run inside the case should be at the same height as the 
appliance inlet pipe in order to clear the fan. If intending to 

fi

 t an internal isolating valve, check that it will be clear of the fan.

Use only new black iron or steel pipes or copper tubing if acceptable—check local codes. Note that in USA, copper tubing 
must be internally tinned for protection against sulfur compounds.
Unions in gas lines should be of ground joint type.
Sealant used must be resistant to the action of all gas constituents including LP gas. Sealant should be applied lightly to 
male threads to ensure excess sealant does not enter gas lines.

11.3 Pressure Testing the Supply Line for Leaks

The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure 
testing of that system at 

test pressures in excess of 1/2 psig (3.5 kPa)

.

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any 
pressure testing of the gas supply piping system at 

test pressures equal to or less than 1/2 psig (3.5 kPa)

. Failure to do 

so will damage the appliance’s gas valve. Such damage is not covered by the manufacturer’s warranty.
When testing for leaks:

Make sure that the appliance is turned off.
Open the manual shut-off valve.
Test for leaks by applying a liquid detergent or soap solution to all joints. 
Bubbles forming indicate a gas leak.

Never use an open fl ame to check for leaks.

Correct any leak detected immediately.

The pressure test tapping locations are shown in the diagram to the right.
A built-in non-adjustable regulator controls the burner manifold pressure. The 
correct pressure range is shown in the Speci

fi

 cations section of this manual. 

The pressure check should be made with the burner lit. See the lighting 
instructions section for full operating details.








BE SURE TO TIGHTEN THE PRESSURE TAP SET-SCREW AFTER CHECKING THE PRESSURE.  

CHECK ALL GAS CONNECTIONS FOR GAS LEAKS.

f i r e - p a r t s . c o m

Содержание 739DVN

Страница 1: ...ge personal injury or loss of life Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING This product must be installed by a licensed plumber o...

Страница 2: ...hecks 23 Operational Warnings 24 Lighting Instructions 25 Maintenance 26 Programmable Remote Control 28 Venting Options 30 Warranty 31 The information contained in this installation manual is believed...

Страница 3: ...t 744FVI Optional Outer Trims 3 sided Contour Trim Kit Kit 746 3 sided Deluxe Trim Kit Kit 747 4 sided Contour Trim Kit Kit 748 4 sided Deluxe Trim Kit Kit 749 Additional Optional Features Circulating...

Страница 4: ...nces Appliance Dimensions See Page 9 for clearance information 28 3 8 R 1 12 19 1 2 2 5 8 36 1 2 26 5 8 9 1 4 Gas Line 7 3 8 Electrical 20 12 5 8 with Contour Outer Trim 12 with Deluxe Outer Trim 10 w...

Страница 5: ...ice technician to inspect the heater and to replace any part of the control system and any gas control which has been under water The appliance area must be kept free from combustible materials gasoli...

Страница 6: ...t when doing any heavy lifting 2 3 Vent Safety Venting must be installed according to local codes and good venting practices 2 4 Electrical Code These appliances when installed must be electrically gr...

Страница 7: ...urpose of input adjustment 10 5 in w c 2 6 kPa 14 0 in w c 3 5 kPa Orifice size Bray CAT 82 650 Bray CAT 92 260 Maximum input rating 24 000 BTU hr 24 000 BTU hr High altitude US 0 2 000 ft 0 610 m US...

Страница 8: ...d components necessary to complete the installation Check that the gas and electrical supplies are ready Prepare opening clean chase level base etc Install vent Install base unit and connect vent Inst...

Страница 9: ...incial state or local codes The section 6 2 shows the minimum install dimensions for the model 739 Note The model 739 is certified without requiring a hearth projection although local codes may requir...

Страница 10: ...Materials Combustible materials Material such as wood compressed paper plant fibers plastics or any material capable of igniting and burning whether flame proofed or not plastered or un plastered Non...

Страница 11: ...rt Maximum vertical height 30 ft measured to bottom of termination Minimum vertical height 10 ft measured to bottom of termination Maximum horizontal run 4 ft measured center to center of pipe Maximum...

Страница 12: ...vent pipe from the outlet of the appliance to termination allow for any offsets in the chase and sufficient vertical height above the roof Apply RTV sealant to the appliance s vent pipe and slide ove...

Страница 13: ...ntains 3 pieces 1 Remote control kit handset receiver and wires 4 1 5 V AA batteries 1 9 V battery 2 Side shroud mounting brackets 1 Top shroud mounting bracket 1 Gas inlet pipe connection adapter 1 R...

Страница 14: ...14 Pack Contents Rear Log Rest Remote Control Ceramic Log Set 742CFB Cast Iron Front 741SFB Standard Metal Front Ceramic Brick Pack 739DVN or 739DVP Engine Engine Pack fire parts com...

Страница 15: ...through the IGN position to PILOT A spark should flash across from the pilot electrode to the pilot burner shield as shown below Appliance Preparation Do not remove the window when the appliance is h...

Страница 16: ...he board is in line with the tab on the wiring harness plug Connect the wires A with the L terminals to the connectors B on the control valve Please note that the connectors are different sizes the sm...

Страница 17: ...at the left side of the control unit Supply line connection to the inlet pipe is 3 8 NPT If the circulating fan is to be installed be aware that the supply pipe run inside the case should be at the s...

Страница 18: ...e lower ledge and be flat against the rear of the firebox Slide the Left Ceramic Panel against the left side of the firebox and up to the Rear Ceramic Panel The Panel will have to be angled to fit ins...

Страница 19: ...re 13 4 Place the Left Side Center Log in position locating the thick part on the left side of the Ash Bed on the 2 pins provided with its nose resting on top of the Ash Bed center projection See figu...

Страница 20: ...ion Rear Log Rest See no 2 on p 18 Rear Log Pins Left Center Log Pins Front Support Ash Bed Rear Log Front Log Left Center Twig Right Center Twig Cross Twig 13 3 13 4 13 5 13 6 13 7 13 8 13 9 13 2 13...

Страница 21: ...14 1 above for window refitting 1 2 3 4 1 2 3 Window Refitting 15 1 Burner Pilot Checks Check ignition pilot stability burner flames and the full range of the thermostat settings using the rotary swit...

Страница 22: ...The brackets will mount flush to the bottom inside corner of each side section Attach the complete trim unit to the firebox with four screws as shown in figure 16 1c 16 2 741SFB Standard Metal Front S...

Страница 23: ...ssociated with the varying sulfur content of the gas You may have the problem for a time and then not see it for many months when it will reappear in your area We have discussed this problem with cera...

Страница 24: ...echnician to inspect the appliance and replace any part of the gas control system which has been under water DO NOT use this appliance if you smell gas WHAT TO DO IF YOU SMELL GAS OPEN WINDOWS DO NOT...

Страница 25: ...flame adjustment knob as far clockwise as possible 3 Turn the gas control knob clockwise to OFF NOTE The knob cannot be turned from PILOT to OFF unless it is pushed in partially Do not force 4 Wait f...

Страница 26: ...Lift up and unhook the upper casting and lower casting If you have difficulties removing either front please refer to section 16 Remove the bottom center spring loaded bolt Turn the 5 remaining spring...

Страница 27: ...trees or other object do not obstruct it Examine the whole vent system regularly using a qualified agency We recommend an annual inspection 20 5 General Servicing If your appliance requires any servic...

Страница 28: ...button sets the hour the button sets the minutes Set the time Note You must start setting the time while the F is flashing If it stops flashing go back to 1 The display shows C 24 hour or F 12 hour To...

Страница 29: ...re Press the TIMER button and hold it until P1 appears and flashes Let go While flashing push the buttons hour and minutes to set the time at which you want your fireplace to turn on in the morning Pr...

Страница 30: ...AL ADAPTER 923GK ALUMINUM FLEXIBLE LINER 3 DIAMETER 2280 Series 3 ACFL NOTE 2 ply liner approved to CAN ULC S635 suitable for venting gas appliances As manufactured by Z Flex Notes 1 Simpson Dura Vent...

Страница 31: ...sehold equipment or appliances iii Damage due to chemicals dampness condensation or sulphur in the fuel supply lines which exceeds industry standards This warranty does not cover glass log breakage or...

Отзывы: