background image

 

 

15

5.

 

SUPPLY GAS 

Heater engine unit #534EAN is used with all natural gas installations. 
Heater engine unit #534EAP is used with all propane installations. 
The supply pressure must be between the limits shown in section 3.2 of this manual. 
The supply connection is 

3

/

8

’’NPT. 

The opening for the gas supply line is at the rear left corner of the appliance. 
 

6.

 

PACK CONTENTS 

See figure 19 

#534EAN or #534EAP Engine unit  

Appliance engine unit fitted with window 

1 Ceramic 

ash 

bed 

5 Ceramic 

logs 

Firebox ceramic rear wall 

Firebox ceramic side walls 

Wall switch & plate (wired) 

1 Wire 

harness 

1 Battery 

holder 

4 1.5V 

AA 

batteries 

1 Port 

cover 

Frame side fixing brackets 

Ash bed rear support 

Restrictor plates type “A” 

Restrictor plates type “B” 

Restrictor plates type “C” 

Gas inlet pipe connection adapter 

Top heat shield panelwith blanking plate 

Frame top support angle 

2 Stand-off 

brackets 

Screws for wall switch plate 

Screws for frame side fixing brackets 

Screws for top heat shield panel 

Screws for frame top support angle 

Screws for stand-off brackets 

Screws for vent fixing 

Woodscrews for fixing appliance to studding  

 

#601SFB Standard metal front (Alternative)

 

1 Upper 

louver 

unit 

1 Lower 

louver 

unit 

2 Side 

channels 

2 Hinge 

studs 

2 Hinge 

spacers 

2 Magnet 

counterplates 

 

#602CFB Cast iron front (Alternative) 

1 Top 

casting 

unit 

1 Bottom 

casting 

unit 

#553RCK Remote control unit (Additional option) 

1 Receiver 

unit 

Remote control hand unit 

1 9V 

Battery 

 

#609WEK Wall switch extension wires (Additional 
option) 

10ft long extension wire harness 

 

 

#551DVK Standard horizontal through-the-wall vent 
kit

 

(Alternative to Dura-vent unit)

 

Vent pipe & terminal unit 

2 Wall 

plates 

Wall shields (Supplied flat) 

12  Thread cutting screws 

Styrofoam cutting support do-nut 

8 Wood 

screws 

8 Wall 

plugs 

 

#555CFK Circulating fan kit (Additional option)

 

Details are with the kit 
 

#603FSK Black or #604 Champagne Additional 
optional 3 sided trims

 

1 Top 

trim 

2 Side 

trims 

Trim fixing brackets 

2 Corner 

connection 

plates 

Grub screws for corner connections 

10   Screws for side trims & engine attachment 
 

#605FSK Black or #606FSK Champagne Additional 
optional 4 sided trims

 

Top & bottom trims 

2 Side 

trims 

Trim fixing brackets 

4 Corner 

connection 

plates 

16  Grub screws for corner connections 
10   Screws for side trims & engine attachment 

 

 
Take care when removing the contents from the packaging to prevent damage. Check that all the contents are in the packs and 
are undamaged. 
 
 
 
 
 
 
 
 
 

Содержание 534AN

Страница 1: ...nt Installation and service must be performed by a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured mobile home...

Страница 2: ...13 4 15 Top Vent Connection Offset and Through the Roof Termination 13 4 16 Vent Location 14 5 SUPPLY GAS 15 6 PACK CONTENTS 15 7 APPLIANCE PREPARATION 17 7 1 Window Removal 17 7 2 Ignition Spark Chec...

Страница 3: ...r flammable vapors and liquids Never attempt to burn paper or any other material in the appliance The venting terminal must not be recessed into a wall or siding The vent terminal on the outside wall...

Страница 4: ...ion in areas where natural gas was not available at the time of initial installation 2 4 Venting options 2 4 1 Direct vent installations One or more of the accessories listed below must be used for ea...

Страница 5: ...clearance B 7 178mm 8 203mm 9 229mm 10 254mm 11 279mm 12 305mm 14 356mm Figure 1 Major dimensions clearances without optional trims Shown with 601SFB Front 3 sided trims 4 sided trims Figure 2 601SFB...

Страница 6: ...These appliances when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical...

Страница 7: ...K only The horizontal vent run can not be extended by the use of any vent accessory pipes 4 3 Rear Vent Connection Flat on Wall with Snorkel Termination See figure 6 For use on horizontal installation...

Страница 8: ...tical pipe run and at sides of horizontal pipe run 2 5 1cm For installations with a horizontal rear termination the combination of horizontal and vertical vent pipes must be within the allowed area sh...

Страница 9: ...on See figure 10 Adapter 817VAK one 90 vent elbow 990B Dura vent pipe lengths a vertical vent terminal and roof flashing will be required Various other ceiling or roof items may be necessary depending...

Страница 10: ...ng on the particular installation See venting options section of this manual Note 1 The distance from the roof to the lowest terminal discharge opening depends on the roof pitch and must be in accorda...

Страница 11: ...izontal pipe run inside building Outside wall shields thimbles 1 12 7cm G Clearance to combustible materials below horizontal pipe run 15 16 3 3cm H Clearance to combustible materials all round vertic...

Страница 12: ...sional requirements in sections 4 10 and 4 11 apply Adapter 817VAK one 90 vent elbow 990B a Dura vent snorkel termination and Dura vent pipe lengths will be required 942 Dura vent thimble kit may also...

Страница 13: ...vent elbows 945B wall straps a vertical vent terminal roof flashing and Dura vent pipe lengths will be required Various other ceiling or roof items may be necessary depending on the particular install...

Страница 14: ...ensation on window 12 30 D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet 60 cm from the center line of the terminal 18 46 E Clearance to unv...

Страница 15: ...to studding 601SFB Standard metal front Alternative 1 Upper louver unit 1 Lower louver unit 2 Side channels 2 Hinge studs 2 Hinge spacers 2 Magnet counterplates 602CFB Cast iron front Alternative 1 T...

Страница 16: ...16 Figure 19 Pack contents...

Страница 17: ...clockwise through the IGN position to PILOT A spark should flash across from the pilot electrode to the pilot burner shield See figure 21 7 3 Flame Control Motor Check See figure 22 Fit the battery ho...

Страница 18: ...collars to check alignment Tighten the 12 screws to secure the outer collar 6 Fit the cover plate and seal Removed from the rear to the top vent opening with 12 screws 7 5 817VAK Pipe Adapter Fitting...

Страница 19: ...es by refitting the two screws at the top rear corners and by two screws from the pack fitted near the front 6 Bend the two top rear stand offs and fit to the heat shield with three screws each see fi...

Страница 20: ...opening set at Less than 3ft 91cm A Maximum Top From 3ft 91cm to 6ft 183cm A Minimum Less than 3ft 6 107cm A Maximum Horizontal through wall Rear From 3ft 6 107cm to 6ft 183cm A Minimum Less than 20f...

Страница 21: ...ing through two holes each side with the woodscrews supplied The top support angle should abut the wall finish but is not fixed to the framing 3 Check the wall finish requirements with the homeowner I...

Страница 22: ...position e Cut the vent tubes squarely to length f Make sure that all Styrofoam is removed from the vent unit after cutting 2 Free the appliance from the frame studding by removing the four screws ins...

Страница 23: ...tube will pass clearly through the plate with the wall shield at the top Place the inner wall plate over the terminal unit 3 Slide the appliance terminal into the wall Make sure that the drain hole i...

Страница 24: ...through the roof If directly above the position where it penetrates the ceiling drop a plumb from the roof to the small hole in the ceiling and mark the roof at this spot If rafters or other obstructi...

Страница 25: ...ase through the opening at the bottom right side of the heater case 2 Cut off the L terminals from the switch wires on the remote control receiver and remove insulation from approximately at ends of w...

Страница 26: ...the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than psig 3 5kPa f Failure...

Страница 27: ...behind the burner See figure 50 2 Place the rear log in position locating the two top projections in the ash bed into the holes in the rear log See figure 51 3 Place the two front logs at the front of...

Страница 28: ...nce and all other controls wall switch remote hand unit See owner s lighting instructions further on in this manual for full details Aeration adjustment As described in section 11 for natural gas appl...

Страница 29: ...nit using the hinge studs and hinge spacers as shown in figure 59 2 Fix the two adhesive backed magnet counterplates to the tabs at the firebox sides which line up with the magnets on the lower louver...

Отзывы: