16.13 To remove the main burner injector.
(See figure 52).
1.
Remove the burner (See section 16.12).
2.
Remove the burner clamping screw (See figure
52).
3.
Unscrew the injector from the burner
4.
Refit in the reverse order.
16.14 To remove the appliance from the fireplace.
1.
Remove the burner unit (See section 16.6).
2.
(See section 9 of this guide), slacken the
hexagonal adjusters on the cable retainers and
unscrew the thumbscrews to release the cables.
3.
Refit as described in the relevant installation
sections. Make sure gas soundness, sealing, spillage
test and performance are satisfactory.
Page 49
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE
Figure 52. Main burner
injector removal