13. FULL OPERATING CHECKS
13.1 Check the burner operation.
Repeat the checks conducted in section 11.3.1 and 11.3.2.
Please note:
When first turned on from cold, the flames will appear predominantly blue.
When operating the fire for the first time, some vapours may be given off which could
set off smoke alarms in the vicinity. These vapours are quite normal with new
appliances. They are totally harmless and will disappear after a few hours use
.
13.2 Check for spillage.
1.
Close all doors and windows in the room containing the appliance.
2.
Light the appliance and set the control to its highest heat position.
3.
Leave the appliance on for five minutes.
4.
The smoke match should be placed horizontally into the hotbox at the right hand
side (See figure 31).
The installation is satisfactory if the smoke is drawn into the appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the
maximum setting for a further ten minutes and then repeat the test. If the smoke is
still not drawn into the appliance inspect the sealing to the fireplace surround. If the
sealing is satisfactory but the appliance is
installed with the flue restrictor (See section 9
point 8) remove the restrictor, reseal the appliance
and retest. If smoke is still not drawn into the
appliance
disconnect the appliance and seek
expert advice.
5.
If the above test is satisfactory open all internal
connecting doors, hatches, etc. in the room. Keep
all doors and windows that open to the outside of
the building closed. Recheck for spillage as
above. If an extractor fan is installed in the same
room as the appliance or a connecting room,
check that spillage does not occur with the fan
operating and all doors and other openings
between the fan and the appliance open.
If the smoke is drawn into the appliance, continue
with the installation. If the test is not satisfactory
disconnect the appliance and advise the
customer of the cause of failure
.
Page 30
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 31. Smoke match tube
position (Fascia may differ from
that shown)
A spillage check must be made before leaving the installed appliance with the
customer.
Содержание 757
Страница 14: ...Page 14 INSTALLER GUIDE Baxi Heating U K Limited 2007 Figure 5 Appliance dimensions and clearances...
Страница 16: ...Page 16 INSTALLER GUIDE Baxi Heating U K Limited 2007 Figure 6 Pack contents...
Страница 26: ...Page 26 INSTALLER GUIDE Baxi Heating U K Limited 2007 Figure 27 Hanging bracket locations...
Страница 48: ...Page 48 Baxi Heating U K Limited 2007 OWNER GUIDE...
Страница 49: ...Page 49 Baxi Heating U K Limited 2007 OWNER GUIDE...
Страница 52: ...Baxi Heating U K Limited 2007...