27
4FXM70EN - 8/2022
0 – 10 VDC Input (Volt DC)
Used to remotely control pump with an incoming 0-10 VDC
signal.
Default settings:
0 VDC = 0% motor speed
10 VDC = 100% motor speed
Press SELECT RUN MODE button until
0 – 10 VDC
Input is
displayed in the top line of the display.
To configure the pump, navigate to
0 – 10 VDC
Input menu
by pressing MENU button, then selecting Input Setup, Input
Modes, and then
0 – 10 VDC
Input.
Press UP or DOWN arrow to scroll through 0 – 9 on selected
digit.
Press RIGHT arrow to scroll over to next digit to right. If
you pass your desired digit, you can easily scroll back by
continuously pressing RIGHT button.
Press ENTER to save changes.
Continue this process until all four screens have been
configured.
To navigate back out of the menu structure you must navigate
back out of menu structure. To do this you must select
← Back at bottom of every screen menu until you see Run
Mode screen displayed.