INTRODUCTION
FIELD OF APPLICATION –
INTENDED USE
Vallox Pureo TX air handling units are energy-saving, fully automated,
low-noise and ready-to-operate ventilation units with heat recovery.
Vallox Pureo TX is available in four different models that meet the
volume flow rate requirement of up to 1800 dm³/s. There is an ePM1
60% class filter on the outdoor air side and an ePM10 60% class filter on
the extract air side as standard.
Vallox Pureo TX units are equipped with highly energy efficient, low-
noise, and power-saving fans. Fans that are equipped with EC motors
can be operated by using three fixed speeds, or alternatively by using
the integrated smart controller with the help of air quality sensors.
Vallox Pureo TX units are equipped with cross counterflow heat
exchangers, in which the heat contained in the extract air is recovered
before the air is blown outdoors through the plates. The process is
completed so that the air flows remain separate. Depending on the
operating conditions, more than 80% of the heat contained in the
extract air is recovered before the air is blown outdoors.
Supply air is transmitted to the primary areas (where supply air is
needed) via the duct system. Used air is extracted from the secondary
areas (such as social facilities, toilets, and showers). It flows through
the duct network back to the ventilation unit, where heat is recovered
before the air is discharged outdoors through the exhaust air duct.
Vallox Pureo TX units are only intended for the handling of air and for
performing the following tasks:
• Filtering normally polluted air
• Heating and/or cooling of the air (with accessories)
• Heat recovery
• A combination of the above functions
The intended use also includes the observance of the operating
manual, the manufacturer‘s instructions for individual components, and
the inspection and maintenance intervals stipulated by Vallox.
Vallox Pureo TX units with the standard equipment are designed to be
installed and used in frost-free premises (room temperature > 0°C). The
availability of a frost-free condensate outlet must be ensured on site.
The corrosion resistance class of the housing is C4 in accordance with
ISO 12944. The unit can be used under these conditions.
Application limits:
• Ambient temperature 0-50°C
• Humidity (max.) 95% RH
IMPORTANT
Material damage due to
the unit freezing!
NOTE
Any use other than
the intended use is
prohibited!