30
Filters
Nominal air volume
fl ow (dm³/s)
Number of fi lters
Filter class
Dimensions (mm)
(l x h x w)
Recommended
fi nal pressure
diff erential (Pa)
Vallox Pureo TX 500
Extract air
500
1
ePM10 60 %
490 x 592 x 535
120
Vallox Pureo TX 500
Outside air
500
1
ePM1 60 %
490 x 592 x 535
174
Vallox Pureo TX 900
Extract air
900
1
ePM10 60 %
592 x 592 x 535
120
Vallox Pureo TX 900
Outside air
900
1
ePM1 60 %
592 x 592 x 535
174
Vallox Pureo TX 1300
Extract air
1300
1
ePM10 60 %
592 x 592 x 535
120
Vallox Pureo TX 1300
Extract air
1300
1
ePM10 60 %
287 x 592 x 535
120
Vallox Pureo TX 1300
Outside air
1300
1
ePM1 60 %
592 x 592 x 535
174
Vallox Pureo TX 1300
Outside air
1300
1
ePM1 60 %
287 x 592 x 535
174
Vallox Pureo TX 1800
Extract air
1800
2
ePM10 60 %
592 x 592 x 535
120
Vallox Pureo TX 1800
Outside air
1800
2
ePM1 60 %
287 x 592 x 535
174
TECHNICAL DATA FOR STANDARD FILTERS
MAINTENANCE
SERVICE AND MAINTENANCE OF THE FANS
The unit must be fully isolated from the mains power supply before
all maintenance and cleaning measures. Risk of injury due to electric
shock, moving parts (fan), and hot surfaces.
WARNING
Danger to life due to electric shock!
Be careful during service and maintenance work, because the fans are
very heavy. The fans must be checked for contamination, damage, and
corrosion once in every 6 months or even more frequently depending
on the degree of impeller contamination:
• Regular inspection with periodic cleaning, if required, is necessary
to prevent an imbalance caused by contamination.
• Clean the fan housing.
• Vibration and oscillation-free operation must be ensured.
• Clean the fan with a damp cloth. Do not use aggressive agents that
could damage the paint. High-pressure cleaners
• and jet water are not permitted.
• If water enters the motor: dry off the motor winding before using it
again.
WARNING
Risk of injury due to high unit weight!