IMPORTANT
The ventilation ducts
must not become
twisted.
The connections to the
connectors must be firm
and tight.
The flange connections
must be leakproof and
firm.
If necessary, anti-
vibration mounts can be
used on site between
the base of the unit and
the floor.
MECHANICAL ASSEMBLY
The installation and connection of the unit may only be carried out by
qualified specialists. Electrical connections must be carried out by a
person who has proper professional training and experience in the
relevant accident prevention regulations, as well as other generally
recognised safety and occupational health codes, and is authorised to
perform work on the unit.
DANGER
Danger to life due to electric shock!
The Vallox Pureo TX air handling unit must be installed in the upright
position. Due to noise levels, which vary depending on system
pressure, it is recommended that the unit be installed in the utility
room or a storage room. It must be ensured that there is a wastewater
connection in the installation area. See the condensate outlet (pages
16-17)
.
The assembly should be implemented in a way that enables the
shortest possible ventilation ducts and a trouble-free connection to the
unit. Tight bends result in increased pressure losses and flow noises.
The unit can be turned by 180° for optimal installation.
Ensure that the unit is positioned on an even surface before starting
the installation work.
Assembly area
Ensure that there is sufficient space for maintenance when installing
the unit.
A Minimum distance to the wall
B Width of the unit
C Minimum distance for opening the service door
D Height of the unit
NOTE
It can be easier to install
accessories prior to the
final positioning and
installation of the unit,
as both sides of the unit
can then be accessed.
A
B
D
C
ASSEMBLY DIMENSIONS
Dimensions (mm)
A
B
C
D
Vallox Pureo TX 500
665
870
870
1662
Vallox Pureo TX 900
795
890
890
1982
Vallox Pureo TX 1300
815
1520
1520
2030
Vallox Pureo TX 1800
815
1720
1720
2030