MAINTENANCE
INS
TALLA
TION
CONDENSATE OUTLET
The humidity contained in the extract air condenses to water during
the heating cycle. Large volumes of condensate can build up in new
buildings when a large number of people is present. The condensate
collected in a stainless steel condensate tray is discharged via two
condensate outlets.
IMPORTANT
The drainage pipe must not be routed above the siphon. The
condensate must flow out easily. If the automatic discharge of
the condensate is not ensured, a suitable condensate pump
must be used.
The condensate outlet must be frost-proof!
• Vallox Pureo TX units have two condensate outlets per condensate
outlet pipe, one on the left and one on the right side of the unit.
Connect the condensate pipe of the corresponding condensate
outlet in the service direction.
• Ensure that any unused condensate outlets are plugged.
The unit has two condensate outlet pipes: one in the supply air side
and one in the exhaust air side. It must be ensured that the condensate
outlet pipes are connected separately. The condensate pipes must only
be connected to the wastewater system via an odour trap (siphon).
The condensate must flow freely into the wastewater system after the
siphon. Existing drainage systems must not be directly connected to
the wastewater system.
NOTE
A ball siphon is available
as an accessory.