BASIC/FACTORY SETTINGS
Basic setting
Factory setting (Air Flow Control) Factory setting (Pressure Control)
Fan control (Constant Speed)
Active
Low speed setpoint
20%
High speed setpoint
100%
Digital and analog control (External Control) 0–10 VDC
Active
Constant Pressure Control
Inactive
Pressure Low Setpoint
-100 Pa
Pressure High Setpoint
-300 Pa
Constant Flow Control
Inactive
Low Flow Setpoint
0.1 m³/s
High Flow Setpoint
0.5 m³/s
K value, Constant Flow
16.7
Exxeo 150 = 12.5
Exxeo 300 = 16.7
Exxeo 700 = 22.2
Exxeo 1400 = 44.4
Exxeo 2000 = 66.7
Exxeo 2500 = 147.2
Exxeo 4100 = 147.2
Outdoor temperature, Compensation start
5°C
Outdoor temperature, Compensation stop
-20°C
Maximum temperature drop for compensation (Temp Drop)
30%
Address
1
Baud Rate
192
Parity Bit
EuEn
Modbus Stopbits
1
P value
20
Exxeo 150 = 5
Exxeo 300 = 10
Exxeo 700 = 20
Exxeo 1400 = 20
Exxeo 2000 = 30
Exxeo 2500 = 75
Exxeo 4100 = 100
Exxeo 150 = 5
Exxeo 300 = 10
Exxeo 700 = 20
Exxeo 1400 = 20
Exxeo 2000 = 20
Exxeo 2500 = 20
Exxeo 4100 = 20
Integration time (I value)
5
Exxeo 150 = 2
Exxeo 300 = 3
Exxeo 700 = 5
Exxeo 1400 = 5
Exxeo 2000 = 10
Exxeo 2500 = 30
Exxeo 4100 = 40
Exxeo 150 = 2
Exxeo 300 = 3
Exxeo 700 = 5
Exxeo 1400 = 5
Exxeo 2000 = 5
Exxeo 2500 = 5
Exxeo 4100 = 5