background image

6

The fan can be controlled by 0–10 VDC analog control 

or by digital control. You can choose two limit values for 

the fan control. The Low value specifies the minimum 

fan control percentage and the High value specifies 

the maximum fan control percentage. If analog control 

(0–10 VDC) is used, the minimum fan control percentage 

equals 0 VDC and the maximum fan control percentage 

equals 10 VDC. If digital control is used, the minimum 

fan control percentage = Ext L is active and the 

maximum fan control percentage = Ext H is active. See 

section 1.5 for the fan control options.

Use the + button to proceed to the fan control menu. 

Use the Menu button to proceed to the setting mode. 

Use the +/– buttons to select On or Off. Press Menu to 

confirm the setting. Selecting Off takes you back to the 

main menu (in the basic model, the On status is always 

active).

Selecting On opens the Low Speed Setpoint menu for 

setting the minimum fan control percentage. Use the 

Menu button to proceed to the setting mode. Set the 

desired value using the +/– buttons (0...100%). The Low 

Speed Setpoint percentage cannot be higher than the 

High Speed Setpoint percentage. Press Menu to confirm 

the setting. 

Use the + button to proceed to the High Speed Setpoint 

menu for setting the maximum fan control percentage. 

Use the Menu button to proceed to the setting mode. 

Set the desired value using the +/– buttons (0...100%). 

The High Speed Setpoint percentage cannot be lower 

than the Low Speed Setpoint percentage. Press Menu 

to confirm the setting. 

Use the + button to proceed to the return menu.

Use the Menu button to return to the Main menu. If the 

status is active, there is a dot in the bottom right corner 

of the display.

1.3  

Constant Speed menu

MANU

AL

+/

Menu

Menu

+

Menu

Menu

+

Menu

+/

+

Содержание Exxeo

Страница 1: ...Control panel manual Document D11350 Valid from 01 12 2023 Updated 18 10 2023 MANUAL Model Vallox Exxeo Vallox Exxeo DPC...

Страница 2: ...fan to open the Function menu on the control panel Main menus 1 Function MANUAL 2 Display 3 Modbus 4 PI only in the DPC model 5 Fan 6 Calibration only in the DPC model 7 Reset Use the buttons to move...

Страница 3: ...minimum extract air chamber pressure and the High value specifies the maximum extract air chamber pressure If analog control is used 0 10 VDC the minimum extract air chamber pressure equals 0 VDC and...

Страница 4: ...s in an incorrect air flow measurement result 1 2 Constant Flow menu Press the Menu button to open the Constant Pressure menu Use the Menu button to proceed to the setting mode Use the buttons to sele...

Страница 5: ...the setting mode Use the buttons to set the desired value 0 01 5 m s The High Flow Setpoint cannot be lower than the minimum air flow Press Menu to confirm the setting Use the button to proceed to the...

Страница 6: ...akes you back to the main menu in the basic model the On status is always active Selecting On opens the Low Speed Setpoint menu for setting the minimum fan control percentage Use the Menu button to pr...

Страница 7: ...tion requires installing the NTC 2 sensor outdoors Selecting Off takes you back to the Main menu If you select On the Compensation Start menu opens Use the Menu button to proceed to the setting mode U...

Страница 8: ...Use the buttons to select On or Off Press Menu to confirm the setting If digital and analog control are Off Constant Pressure Constant Flow and fan control use the minimum setpoint If the status is ac...

Страница 9: ...e Pressure menu The menu will not open if the control is not fitted with a pressure sensor Use the Menu button to view the pressure sensor reading Pa Use the Menu button to return to the Main menu 2 D...

Страница 10: ...ting mode menu Use the Menu button to view the mode setting On the minimum value has been selected Off no minimum value has been selected Use the Menu button to return to the Main menu 2 6 Digital inp...

Страница 11: ...etting C If the display shows no reading no NTC sensor has been connected Use the Menu button to return to the Main menu Use the button to proceed to the return menu Use the Menu button to return to t...

Страница 12: ...address 1 247 Press Menu to confirm the setting Use the button to proceed to the Baud Rate menu Use the Menu button to proceed to the setting mode Use the buttons to set the desired value 96 192 384 N...

Страница 13: ...fan air flow or pressure I value menu The menu can be used to control the Integrator gain The higher the I value the less impact it has on the control and the exact setpoint may not be reached The low...

Страница 14: ...Use the button to proceed to the Integration time menu Use the Menu button to proceed to the setting mode Use the buttons to set the desired value 5 90 4 2 Integration time menu I Value 4 1 Proportion...

Страница 15: ...right corner of the display Use the button to proceed to the return menu Use the Menu button to return to the Main menu 5 2 Error data based on the status information Status Press the Menu button to o...

Страница 16: ...he buttons simultaneously for at least three seconds to perform the calibration When the calibration is complete the display shows 0000 for five seconds The Calibration menu appears automatically afte...

Страница 17: ...conds to reset the settings When the settings have been reset the display shows for five seconds The Reset menu appears automatically after this If you do not wish to reset the settings press Menu to...

Страница 18: ...Exxeo 700 22 2 Exxeo 1400 44 4 Exxeo 2000 66 7 Exxeo 2500 147 2 Exxeo 4100 147 2 Outdoor temperature Compensation start 5 C Outdoor temperature Compensation stop 20 C Maximum temperature drop for com...

Страница 19: ...air compensation stop R W I16 c 30 10 20 1013 Outdoor air temperature compensation drop R W I16 5 90 30 1014 Ext control mode R W U8 2 0 10V in 1 L H 0 Modbus 1 1015 Measured pressure value R I16 Pa...

Страница 20: ...er R I16 2008 Actual fan speed request of 0 10V R U16 0 1 0 1000 2009 Fan RPM R I16 rpm Constant flow mode related registers for monitoring etc Holding register Description R RW Datatype Unit Range De...

Отзывы: