10
2.4
Analog Input menu
Use the + button to enter the digital input maximum
setting mode menu.
Use the Menu button to view the mode setting. On
= the maximum value has been selected, Off = no
maximum value has been selected.
Use the Menu button to return to the Main menu.
Use the + button to proceed to the Analog Input menu.
Use the Menu button to proceed to the analog input
value (VDC).
Use the Menu button to return to the Main menu.
2.5 Digital input minimum value status menu
(External Input L)
Use the + button to enter the digital input minimum
setting mode menu.
Use the Menu button to view the mode setting. On
= the minimum value has been selected, Off = no
minimum value has been selected.
Use the Menu button to return to the Main menu.
2.6 Digital input maximum value status menu
(External Input H)
Press + to proceed to the Alarm menu.
Use the Menu button to view the alarms. Use the +/–
buttons to move in the menu.
0= no alarms
Er01 = control setting not achieved
Er02 = pressure sensor not responding
Er03 = NTC 1 error
Er04 = NTC 2 error
Er05 = EXTL and EXTH active simultaneously
Er06 = fan speed (RPM) cannot be read from the
actuator
Er07 = on/off status cannot be read from the actuator
2.7
Alarm menu
Use the Menu button to return to the Main menu.
MANU
AL
+/
–
Menu
Menu
+/
–
Menu
Menu
Menu
Menu
+
Menu
Menu
+
Menu
+
Menu
+