VALLOX DIGIT2 SE

7

INSTRUCTIONS FOR USE

© VALLOX • We reserve the right to make changes without prior notice.

Remember!

Switch post-heating off when it starts
to get too warm in the dwelling becau-
se of warm weathers.
Switch post-heating on again when it
gets cooler in autumn.

2.12. Heat recovery antifrost function and preheating

•  Antifrost prevents the heat recovery cell from freezing, thus ensuring proper ventilation even in

cold periods.

•  According to the factory setting antifrost is implemented in units with an electric preheating

radiator by stopping the supply air fan. The stopping function is controlled on the basis of the
data given by the temperature sensor measuring the temperature sensor of exhaust air after
the heat recovery cell.

•  T he supply air fan stops when exhaust air temperature falls to the setpoint (factory setting

+4 

°

C) and starts when exhaust air temperature has risen to the value set (by the amount of the

hysteresis setting, factory s3 

°

C).

Preheating

•  The unit is equipped either with an electric preheating radiator or a liquid-circulating

preheating radiator (MLV model). The purpose of using the radiator is to minimise momentary
stopping of the supply air fan. This ensures a maximally even supply air flow through the unit.

•  An electric preheating radiator is taken into use by using the Settings menu, adjusting switch-

on temperature to be higher than the value for “supply fan Stop”. The difference could be

°

C, for example.The radiator switches on when exhaust air temperature falls to the setpoint

and switches off when exhaust air temperature has risen to the value set (by the amount of the
hysteresis setting, factory s3 

°

C).

If radiator power is not sufficient in extreme conditions, the supply fan starts to stop as exhaust
air temperature goes down to the “supply fan Stop” value. The setpoint for preheating could
be +6 

°

C, for instance; the factory setting for “fan Stop” is +4 

°

C.

•  The liquid-circulating preheating radiator (MLV model) starts when post-heating has been

switched on and outdoor air temperature is below the preheating setpoint. The setpoint
temperature must be lower than the temperature of the liquid in the ground collector (factory
s0 

°

C). The automatic control system of the unit switches on the circulation pump and

opens the solenoid valve of the radiator (see the Technical specification).

2.13. Maintenance reminder

•  The maintenance reminder switches on the maintenance reminder symbol ( ) in the main

display of the control panel at defined intervals, the factory setting being 4 months.

•  The maintenance reminder symbol is reset at the control panel (see the instructions for using

the control panel, Section 3.3.10.).

•  The interval can be set between 1 and 15 months at the control panel.

2.14. Filter guard function

•  If DIGIT2 SE is equipped with a pressure difference switch for the supply and/or extract air

ductwork, the switch monitors the pressure difference in the whole ductwork. When pressure
has risen (e.g. because of a clogged filter), the filter guard symbol ( ) in the main display of
the control panel is lit up.

•  The filter guard closes the contacts of the fault signal relay, and the filter guard symbol ( ) is

seen in the main display.

•  The maintenance reminder is on even during this function.
•  The operation threshold for the pressure difference switch is adjusted at the pressure

difference switch regulator (0...500 Pa). Factory setting is ca. 260 Pa, and the setting can be
changed if needed. With clean filters, the symbol should light up at speeds 7 and 8.

2.15. Antifreeze function in water-circulating post-heating unit

•  The antifreeze function aims at preventing a water-circulating post-heating unit from freezing.

The automatic function stops the supply and extract air fans as soon as outdoor air
temperature falls below 0 

°

C and supply air temperature below +7 

°

C. At the same time, the

self-actuated dampers of the fans close and the control valve becomes wide open. The control
panel displays the fault message FREEZING ALERT, irrespective of display.

•  The fans start automatically and the dampers open as soon as supply air temperature exceeds

10 

°

C.

Pressure difference switch

Содержание DIGIT2 SE VKL

Страница 1: ...OR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY MODELS VALLOX DIGIT2 SE VALLOX DIGIT2 SE VKL VALLOX DIGIT2 SE MLV VKL VALLOX DIGIT2 SE MLV electric VALLOX We reserve the right...

Страница 2: ...nu p 9 3 3 Settings menu p 10 3 4 Week clock control p 12 3 5 Factory settings p 12 4 MAINTENANCE INSTRUCTIONS 4 1 Filters p 13 4 2 Fans and post heating radiator p 14 4 3 Filter guard p 14 4 4 Conden...

Страница 3: ...During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in the toilet as well 1 3 How much air i...

Страница 4: ...with a wireless controller option or with a LON converter option The standard week clock control can be used to control the fan power of the unit and the setpoint for supply air temperature This func...

Страница 5: ...the highest measuring result Carbon dioxide control is anticipatory When carbon dioxide content is on the rise it raises speed up to speed 4 even if the setpoint were not exceeded 1 5 carbon dioxide...

Страница 6: ...perature difference gets smaller the period of active heating is automatically reduced in two minute sequences The adjustment range of heating is 10 30 C The heating radiator is on when the sign is di...

Страница 7: ...model starts when post heating has been switched on and outdoor air temperature is below the preheating setpoint The setpoint temperature must be lower than the temperature of the liquid in the ground...

Страница 8: ...tch raises the fan speed to the set maximum speed for 45 minutes The function is started in the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seco...

Страница 9: ...tive when the indicator is not lit 3 1 Keyboard Power failure After a power failure the unit starts at minimum fan speed The adjustments and setpoints chosen will remain in the memory of the unit in s...

Страница 10: ...adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance...

Страница 11: ...basic humidity level Basic RH level 40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in...

Страница 12: ...na bath is taken after which fan speed is lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finish...

Страница 13: ...cuuming them 2 to 4 times a year and whenever the maintenance reminder or filter guard indicates a need for maintenance When you open the door of DIGIT2 SE the security switch T turns voltage off The...

Страница 14: ...SE can be equipped with an optional filter guard The filter guard symbol normally lights up in the main display at speeds 7 and 8 when the filters are clean and this does not require any maintenance...

Страница 15: ...he stopping and starting tem peratures by 1 or 2 C It extends the period between the stopping and starting of the supply air fan See the instruc tions for using the control panel Section 3 3 22 If the...

Страница 16: ...ss tube fuse located in the control card behind a protecting plate protecting the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube f...

Отзывы: