The preheating temperature for the antifrost function of the heat recovery cell is chosen
with the + and – buttons. 

MLV model:

 Choose outdoor air temperature at which preheating

is on. (Note! Temperature < the temperature of the liquid circulating in the radiator.)

3.3.24. Pre-heating temperature for antifrost function in the heat recovery cell

Preheater
07C

VALLOX DIGIT2 SE

11

INSTRUCTIONS FOR USING THE CONTROL PANEL

© VALLOX • We reserve the right to make changes without prior notice.

The hysteresis of the antifrost function in the heat recovery cell is selected with the + and – buttons.

3.3.22.  Hysteresis of antifrost function in heat recovery cell

Hysteresis
03C

The interval for the maintenance reminder is selected with the + and – buttons. The
maintenance reminder interval refers to months.

3.3.21.  Choosing maintenance reminder interval

Maintenance rem.
04

A water or electric radiator is selected with the + and – buttons, depending on the type of post-
heating radiator the unit is equipped with.

Note! Choosing the wrong type of post-heating may cause a faulty post-heating function.

3.3.20. Choosing post-heating for the unit

Radiator type
electric rad.

The basic humidity level can be chosen as either automatic or manual.
The selection is done with the + and – buttons.

3.3.19. Choosing basic humidity level

Rh-level setting
automatic

The desired setpoint is chosen with the + and – buttons when manual adjustment has been selected
as the Rh level setting (humidity setting, Section 3.3.19).

3.3.16. Setpoint of the basic humidity level

Basic %RH level
40%

The desired cell bypass temperature is selected with the + and – buttons. If outdoor temperature
is lower than cell bypass temperature, the summer/winter damper is in the winter position.

3.3.15.  Changing the operating temperature of heat recovery cell bypass

Cell bypass
10C

The desired adjustment value for the direct current fan is selected with the + and – buttons. The
rotation speed of the supply air fan can be lowered by decreasing the percentage value. If the unit
has alternating current fans, this adjustment has no impact on the functioning of the unit.

3.3.14. Controlling the direct-current fan on supply air side 

(does not apply to VALLOX DIGIT2 SE as it has an AC fan)

DC fan - supply
100%

The mode of operation of the switch (either fireplace or booster switch)
is selected with the + and – buttons.

3.3.17. Mode of operation of the fireplace/booster switch

Switch type
Fireplace switch

Cascade control is chosen to be on or off with the + and – buttons.

3.3.18. Choosing cascade control for supply air temperature

Cascade adjust
Off

The setpoint for CO

2

 adjustment is chosen with the + and – buttons.

3.3.25. Changing the setpoint for carbon dioxide adjustment

CO2-setting
0900 PPM

The desired maximum fan speed is selected with the + and – buttons. Maximum fan
speed is on either with adjustments or always. See Section 3.3.6. Mode of operation
of maximum speed limitation.

3.3.26. Choosing maximum fan speed

MAX speed
8

The stopping temperature of the supply air fan for the antifrost function in the heat
recovery cell is chosen with the + and –buttons.

3.3.23. Stopping temperature of supply air fan for the antifrost function in the heat recovery cell

Supply fan stop
05C

Содержание DIGIT2 SE VKL

Страница 1: ...OR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY MODELS VALLOX DIGIT2 SE VALLOX DIGIT2 SE VKL VALLOX DIGIT2 SE MLV VKL VALLOX DIGIT2 SE MLV electric VALLOX We reserve the right...

Страница 2: ...nu p 9 3 3 Settings menu p 10 3 4 Week clock control p 12 3 5 Factory settings p 12 4 MAINTENANCE INSTRUCTIONS 4 1 Filters p 13 4 2 Fans and post heating radiator p 14 4 3 Filter guard p 14 4 4 Conden...

Страница 3: ...During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in the toilet as well 1 3 How much air i...

Страница 4: ...with a wireless controller option or with a LON converter option The standard week clock control can be used to control the fan power of the unit and the setpoint for supply air temperature This func...

Страница 5: ...the highest measuring result Carbon dioxide control is anticipatory When carbon dioxide content is on the rise it raises speed up to speed 4 even if the setpoint were not exceeded 1 5 carbon dioxide...

Страница 6: ...perature difference gets smaller the period of active heating is automatically reduced in two minute sequences The adjustment range of heating is 10 30 C The heating radiator is on when the sign is di...

Страница 7: ...model starts when post heating has been switched on and outdoor air temperature is below the preheating setpoint The setpoint temperature must be lower than the temperature of the liquid in the ground...

Страница 8: ...tch raises the fan speed to the set maximum speed for 45 minutes The function is started in the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seco...

Страница 9: ...tive when the indicator is not lit 3 1 Keyboard Power failure After a power failure the unit starts at minimum fan speed The adjustments and setpoints chosen will remain in the memory of the unit in s...

Страница 10: ...adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance...

Страница 11: ...basic humidity level Basic RH level 40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in...

Страница 12: ...na bath is taken after which fan speed is lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finish...

Страница 13: ...cuuming them 2 to 4 times a year and whenever the maintenance reminder or filter guard indicates a need for maintenance When you open the door of DIGIT2 SE the security switch T turns voltage off The...

Страница 14: ...SE can be equipped with an optional filter guard The filter guard symbol normally lights up in the main display at speeds 7 and 8 when the filters are clean and this does not require any maintenance...

Страница 15: ...he stopping and starting tem peratures by 1 or 2 C It extends the period between the stopping and starting of the supply air fan See the instruc tions for using the control panel Section 3 3 22 If the...

Страница 16: ...ss tube fuse located in the control card behind a protecting plate protecting the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube f...