2.3.4.

Liquid-circulating preheating and precooling

•  Setting the control temperature (-6 

°

C... +15 

°

C, outdoor air) for the heating function in a

liquid-circulating preheating unit (MLV model). The function is on when outdoor air
temperature goes below the set temperature and post-heating has been switched on (see
the instructions for using the control panel, Section 3.3.24.).
When the temperature value is lower than the temperature of the liquid coming from the
ground collector, the liquid is used to heat outdoor air. If preheating cannot keep exhaust
air temperature warmer than the stopping temperature is, the outdoor air fan stops.

•  Setting the control temperature (+10 

°

C... +30 

°

C, supply air) for cooling in the liquid-

circulating preheating unit (MLV model). The cooling function starts whe the post-heating
radiator has been switched off and the temperature of air coming from the unit to the
dwelling exceeds the setpoint temperature of supply air (see the instructions for using the
control panel, Section 3.2.6.).
When choosing the setpoint temperature for supply air, care must be taken so as not to
bring too cold air into the duct, which may cause humidity damage. The risk is small when
the ground collectors of the heat pump are situated in the ground or in a water system and
the liquid received from them is warmer in summer than the liquid circulating in the drilled
well.
If the duct is not insulated against condensation indoors, the temperature of air travelling
in it must be confined to below the dew point, which depends on the ambient temperature
and relative humidity. In hot weather, supply air temperature should not go below
+16…+20 

°

C.

2.4. Ventilation control with carbon dioxide sensor (option)

•  In carbon dioxide control, VALLOX DIGIT2 SE adjusts fan speed so as to keep carbon

dioxide content in the ventilation zone below the setpoint. When two or more sensors are
used, fan speed is adjusted according to the highest measuring result.

•  Carbon dioxide control is anticipatory. When carbon dioxide content is on the rise, it

raises speed up to speed 4 even if the setpoint were not exceeded.

•  1...5 carbon dioxide sensors can be connected as options to the VALLOX DIGIT2 SE unit.
•  The adjustment is switched on/off and, if needed, the setpoint (500...2000 ppm) is set at

the control panel. The factory setting is 900 ppm. The recommended maximum carbon
dioxide content in good indoor air is 1,000 ppm.

•  When control is on, the control panel may be used to raise fan speed to the maximum fan

speed and to decrease it to the base fan speed. In carbon dioxide control, maximum fan
speed limitation is enabled.

2.5. Ventilation control with humidity sensor (option)

There are two methods for adjusting fan speed.
1

Automatic humidity setting

, which is suitable for controlling humidity in washing rooms, for

instance. The program records current humidity level and selects it as the setpoint, which it
then uses as the target for drying air in a bathroom e.g. after a shower. The setpoint
automatically varies according to season, for instance, and is always at the right level.
This setting is factory selected.

2 Humidity level can also be set 

fixed

. The setting can range between 1...99 %RH and is set

at the control panel. This can be used in public saunas and swimming pools, for instance.
The program aims at keeping humidity at the setpoint. The setpoint can be changed if
needed.
Mode of adjustment is selected at the controller (see the Settings menu, Section 3.3.19.).
Recommended humidity content of good indoor air is approximately 45%.

•  When this control is on, the control panel may be used to raise fan speed to the maximum

fan speed and to decrease it to the base fan speed.

•  In humidity control, fan speed varies between the basic and maximum fan speeds

selected.

•  When the unit is first taken into use with 

automatic setpoint search enabled

 (factory setting), 

it

takes 3 to 10 hours for the program to define the value

. During this time, humidity adjustment is not

enabled (because the first value, selected at the factory, is 100%).

•  Automatic search is enabled even if humidity control is not selected.

Carbon dioxide sensor (CO

2

)

Humidity sensor (RH)

2.4.

2.5.

Содержание DIGIT2 SE VKL

Страница 1: ...OR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY MODELS VALLOX DIGIT2 SE VALLOX DIGIT2 SE VKL VALLOX DIGIT2 SE MLV VKL VALLOX DIGIT2 SE MLV electric VALLOX We reserve the right...

Страница 2: ...nu p 9 3 3 Settings menu p 10 3 4 Week clock control p 12 3 5 Factory settings p 12 4 MAINTENANCE INSTRUCTIONS 4 1 Filters p 13 4 2 Fans and post heating radiator p 14 4 3 Filter guard p 14 4 4 Conden...

Страница 3: ...During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in the toilet as well 1 3 How much air i...

Страница 4: ...with a wireless controller option or with a LON converter option The standard week clock control can be used to control the fan power of the unit and the setpoint for supply air temperature This func...

Страница 5: ...the highest measuring result Carbon dioxide control is anticipatory When carbon dioxide content is on the rise it raises speed up to speed 4 even if the setpoint were not exceeded 1 5 carbon dioxide...

Страница 6: ...perature difference gets smaller the period of active heating is automatically reduced in two minute sequences The adjustment range of heating is 10 30 C The heating radiator is on when the sign is di...

Страница 7: ...model starts when post heating has been switched on and outdoor air temperature is below the preheating setpoint The setpoint temperature must be lower than the temperature of the liquid in the ground...

Страница 8: ...tch raises the fan speed to the set maximum speed for 45 minutes The function is started in the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seco...

Страница 9: ...tive when the indicator is not lit 3 1 Keyboard Power failure After a power failure the unit starts at minimum fan speed The adjustments and setpoints chosen will remain in the memory of the unit in s...

Страница 10: ...adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance...

Страница 11: ...basic humidity level Basic RH level 40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in...

Страница 12: ...na bath is taken after which fan speed is lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finish...

Страница 13: ...cuuming them 2 to 4 times a year and whenever the maintenance reminder or filter guard indicates a need for maintenance When you open the door of DIGIT2 SE the security switch T turns voltage off The...

Страница 14: ...SE can be equipped with an optional filter guard The filter guard symbol normally lights up in the main display at speeds 7 and 8 when the filters are clean and this does not require any maintenance...

Страница 15: ...he stopping and starting tem peratures by 1 or 2 C It extends the period between the stopping and starting of the supply air fan See the instruc tions for using the control panel Section 3 3 22 If the...

Страница 16: ...ss tube fuse located in the control card behind a protecting plate protecting the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube f...

Отзывы: