MAINTENANCE INSTRUCTIONS

4.2. Fans and post-heating radiator

The supply and extract air fans (D and E) have been fastened with rubber
collars (F). When removing the fans for maintenance remove the one-way
dampers (L) from the VKL model, open the ear (K), which is bent over the
rubber collar (F). Then lift the rubber collar off and turn the fan off from above
the lower support (M) made of rubber. Then disconnect the electric connector
(G).
Clean the fan blades with compressed air or with a brush. Each blade has
to be equally clean so that the fans stay balanced. Take care not to remove
the balancing pieces attached to the fan blades.
If you use water in cleaning the unit or its parts, do not let it flow into the
electrical parts.

4.2.1.

Radiators

I

Post-heating radiator: electricity

J

Preheating radiator: electricity

H Post-heating radiator and actuator: liquid
P Preheating radiator: liquid

4.2.2.

Detaching and attaching of self-actuated one-way damper (vacuum

damper), MLV and VKL models

A Put the hook of the damper (Y) rim under the back edge of the fastening

collar (K) of the fan (F). Then push the damper downwards until the
steering edges of the valve go inside the rubber collar.

B Push the other side of the collar with a finger.
C Put the hook of the front edge of the damper below the front edge of the

collar.

To detach the damper take the same steps in the opposite order.

4.3. Filter guard

DIGIT2 SE can be equipped with an optional filter guard. The filter guard symbol ( ) normally
lights up in the main display at speeds 7 and 8, when the filters are clean, and this does not
require any maintenance activities. If the symbol does not light up at speed 8, the pressure
in the ventilation ductwork of the building differs from the factory setting. In that case, adjust
the filter guard setpoint lower in the inside of the unit (see Section 2.14). If the filter guard
symbol lights up at fan speed 4 or 5, the filters need cleaning. If they are clean, the lighting
up may be caused by too dense a mosquito net installed in the external grille, contrary to
what is said in the installation instructions, or by the closing of the supply air valves in the
rooms. If, after checking these things, the symbol continues to light up at small speeds, adjust
the setpoint to a higher value.

4.4. Condensing water

During the heating season, humidity of extract air condenses into condensing water. Water
formation may be abundant in new buildings or if ventilation is low compared to the humidity
build-up caused by the residents. Condensing water needs to flow out from the ventilation
unit without hindrance. In connection with maintenance, e.g. in autumn before the beginning
of the heating season, make sure that the condensing water outlet (L) in the bottom tank is
not clogged. You may check it by pouring a little water in the tank. Clean if necessary.

Do not let water flow into electrical devices.

© VALLOX • We reserve the right to make changes without prior notice.

L

A

B

C

Y

K

F

Y

K

F

Y

K

F

L

G

D

F

M

L

F

G

K

D

M

K

Y

K

F

I

J

Q

Q

H

P

Содержание DIGIT2 SE VKL

Страница 1: ...OR USE AND MAINTENANCE DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY MODELS VALLOX DIGIT2 SE VALLOX DIGIT2 SE VKL VALLOX DIGIT2 SE MLV VKL VALLOX DIGIT2 SE MLV electric VALLOX We reserve the right...

Страница 2: ...nu p 9 3 3 Settings menu p 10 3 4 Week clock control p 12 3 5 Factory settings p 12 4 MAINTENANCE INSTRUCTIONS 4 1 Filters p 13 4 2 Fans and post heating radiator p 14 4 3 Filter guard p 14 4 4 Conden...

Страница 3: ...During the heating season the windows and other outer wall structures remain dry Humidity in indoor air is not condensed in the ventilation ducts Air is fresh in the toilet as well 1 3 How much air i...

Страница 4: ...with a wireless controller option or with a LON converter option The standard week clock control can be used to control the fan power of the unit and the setpoint for supply air temperature This func...

Страница 5: ...the highest measuring result Carbon dioxide control is anticipatory When carbon dioxide content is on the rise it raises speed up to speed 4 even if the setpoint were not exceeded 1 5 carbon dioxide...

Страница 6: ...perature difference gets smaller the period of active heating is automatically reduced in two minute sequences The adjustment range of heating is 10 30 C The heating radiator is on when the sign is di...

Страница 7: ...model starts when post heating has been switched on and outdoor air temperature is below the preheating setpoint The setpoint temperature must be lower than the temperature of the liquid in the ground...

Страница 8: ...tch raises the fan speed to the set maximum speed for 45 minutes The function is started in the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seco...

Страница 9: ...tive when the indicator is not lit 3 1 Keyboard Power failure After a power failure the unit starts at minimum fan speed The adjustments and setpoints chosen will remain in the memory of the unit in s...

Страница 10: ...adjustment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance...

Страница 11: ...basic humidity level Basic RH level 40 The desired cell bypass temperature is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in...

Страница 12: ...na bath is taken after which fan speed is lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finish...

Страница 13: ...cuuming them 2 to 4 times a year and whenever the maintenance reminder or filter guard indicates a need for maintenance When you open the door of DIGIT2 SE the security switch T turns voltage off The...

Страница 14: ...SE can be equipped with an optional filter guard The filter guard symbol normally lights up in the main display at speeds 7 and 8 when the filters are clean and this does not require any maintenance...

Страница 15: ...he stopping and starting tem peratures by 1 or 2 C It extends the period between the stopping and starting of the supply air fan See the instruc tions for using the control panel Section 3 3 22 If the...

Страница 16: ...ss tube fuse located in the control card behind a protecting plate protecting the electronics inside the unit may have blown 12 Check the door switch and fuses The unit includes a T800 mA glass tube f...

Отзывы: