Connection of VKL post-heating radiator to underfloor heating circuit

To minimise the risk of freezing involved in the connection the system has several antifreeze functions.
1. The unit stops if supply air temperature goes below the set temperature and automatically starts as soon as

temperature rises.

2. When the unit stops, the self-actuated dampers (E) close.
3.  The electric valve (T) opens when the unit becomes dead.
4.  The unit issues an alarm of freezing risk at the controller.

Use of VKL post-heating radiator

•  The temperature of heating water shall be adjusted according to the temperature of outdoor air.
•  No water must be led into the radiator of the unit until the system has been adjusted for operation and the heating

network has heating on or it has been otherwise ensured that the radiator will not freeze.

•  Water circulation in the heating network connected to the unit and the circulation pump must not be stopped during

the heating season.

•  The base volume of water flow into the radiator of the unit can be adjusted with valves (R), which can also act as

stop valves (not included in the delivery)..

KP

Circulation pump. Size e.g. 0.07 dm

3

/s,

60 kPa, not included in the delivery
Because of the risk of condensing the pump

should be suitable for pumping liquid colder

than the ambient temperature (e.g.

Grundfors UPS-25-60 180 model K).

MV

Solenoid valve, not included in the delivery.

The valve has to be suitable for the liquid in

the ground collector .

T

Valve, included in the unit delivery

Y

One-way valve, not included in the delivery

(as low pressure loss as possible)

E

Self-actuated dampers, included in the

delivery

IP

Air bleeder (located after the pump and at the

highest point in the system).

Connection of MLV preheating/cooling radiator

The radiator is connected to the pipe coming from the ground collector. When the requirements for starting the heating
or cooling function are met, the control function of the unit opens the solenoid valve (MV) and starts the pump (KP).
Observe the frost resistance of the liquid used in the ground collector. Connection pipes of the MLV radiator have to be
insulated against condensation. 

Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation

insulation should not go below +16...20 

°

C.

Other connections

Heat can be conducted to the post-heating radiator of DIGIT2 SE VKL in other ways than described above. It is possible
to build a separate circuit for the radiator if higher power is desired, or the risk of freezing can be eliminated by using
non-freezing heat transfer solution. For more information, see the instructions for VALLOX VKL connections in internet,
www.vallox.coms.

PIPE CONNECTIONS

RADIATOR HEATING

HEAT PUMP

UNDERFLOOR HEATING

GROUND COLLECTOR

Heating water

adjustment

Содержание Digit 2 SE Series

Страница 1: ...Preheating unit MLV liquid radiator Post heating unit Electric 1200 W 5 2 A Filters Supply air G3 and F7 Extract air G3 Weight 71 kg Ventilation Control panel control adjustment options Week clock co...

Страница 2: ...panel CO2 sensor option LON converter option Air flow measuring outlets behind cover plate Water radiator actuator valve Connection 12 MLV connection 10 cu 20 21 Supply air to the dwelling Extract air...

Страница 3: ...plate You can measure the total pressure of the supply and extract air ductwork at the measurement outlets using a pressure gauge Compare the pressure readings with the air volume curves to see unit a...

Страница 4: ...7 38 9 31 5 68 0 50 1 66 3 62 9 55 4 46 7 45 0 42 3 34 4 24 3 68 2 52 5 64 1 63 4 59 9 48 7 46 8 45 0 37 1 26 5 69 1 54 2 70 2 65 2 60 0 50 6 48 1 47 1 39 2 32 5 71 8 56 1 70 4 66 9 62 2 52 9 50 2 49...

Страница 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Страница 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Страница 7: ...dB LWA dB A 1 16 24 2 25 47 3 36 70 4 48 90 5 58 104 6 68 116 7 75 131 8 87 148 1 25 7 2 38 7 3 46 46 4 59 69 5 72 79 6 82 106 7 92 112 8 104 141 LpA dB A AP qV dm3 s AP supply extract dm3 s ED and SD...

Страница 8: ...WITCH REMOTE MONITORING 1 10 2 3 4 5 6 7 8 9 1 10 16x0 25mm2 1 2 A 2 3 4 REMOTEMONITORING 0 10VDCor0 20mA ha ro L 6 7 FIREPLACESWITCH 6 va vi va ke R ke r r vi 7 5 7018800 2 1 N K K 1 2 r s m r 2N 1 2...

Страница 9: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Страница 10: ...e loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa...

Страница 11: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Страница 12: ...out prior notification CONTROL DIAGRAM ELECTRIC RADIATOR 12 Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor Exhaust air temperature Standard HR antifreeze Adjustment range 6...

Страница 13: ...henever outdoor air temperature falls below the threshold set or when outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of preheatin...

Страница 14: ...reserve the right to make changes without prior notification CONTROL DIAGRAM VKL MODEL 14 Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor Exhaust air temperature Standard H...

Страница 15: ...e sensors TE1 and TE3 preventing the risk of freezing and the intermittent stopping of supply air fan S If the power of preheating unit R2 is not enough or is not on the control centre intermittently...

Страница 16: ...TION PANEL PLUG LON CONVERTER REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT VENTILATION ZONE INTERNAL ELECTRICAL AND CONTROL CONNECTIONS POST HEA...

Страница 17: ...sensor Automatic Adjustment range 1 99 99 Option Humidity control Adjustment interval 1 15 min 10 10 VALLOX We reserve the right to make changes without prior notification 17 PART LIST Parts list VAL...

Страница 18: ...very antifreeze Controlling preheating in a liquid circulating MLV radiator is different from that in an electric preheating radiator The liquid radiator switches on based on the measurement data from...

Страница 19: ...straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate Installation Lift the unit straight upwards till the locking wings on the sid...

Страница 20: ...ivery Because of the risk of condensing the pump should be suitable for pumping liquid colder than the ambient temperature e g Grundfors UPS 25 60 180 model K MV Solenoid valve not included in the del...

Отзывы: