VALLOX DIGIT2 SE/VKL/MLV

1

2

3

4

5

6

7

8

Keyboard

Main display

Paneelin osoite
1

Panel address
1

Control

VALLOX DIGIT SE can be controlled with the control panel coming with the unit (3 at most) and with

optional CO

2

 (5 at most) and %RH sensors (2 at most). Fan speeds of the unit can be controlled via

remote monitoring with a voltage or current signal. In case of disturbances, a potential-free relay

contact signal is issued.
With an optional VALLOX LON converter, the whole operation of the unit can be controlled via remote

monitoring.

Week clock control

The week clock in the control panel of the unit can be used to programme the desired fan power

option (1…8) for each hour in the day.

21 C

3

10:20

Fan speed can be changed in this display with the + and – buttons

3

Scrolling up

With this button, you can scroll
the displays upward.

Scrolling down

With this button, you can scroll
the displays downward.

Increase button

With this button, you can increase values.

Decrease button

With this button, you can decrease
values.

Start button

With this button, you switch the unit on and off. When the
indicator is lit, the unit is on.

Carbon dioxide adjustment

With this button, you set carbon dioxide adjustment on
and off. When the indicator is lit, the adjustment is on.

Humidity adjustment

With this button, you set humidity adjustment on and off.
When the indicator is lit, the adjustment is on.

Post-heating

With this button, you set post-heating on and off. When
the indicator is lit, post-heating is on. The summer function
is active when the indicator is not lit.

1

2

3

4

5

6

7

8

Fan speed (3).
Supply air temperature (21 

°

C).

Post-heating is on.
Time.
Filter guard alert.

Maintenance reminder alert.
Fireplace / booster switch on. The fireplace /
booster switch is activated in this display by
simultaneously pressing down the + and – buttons
for 2 seconds.
Week clock control on.

21 C

10:20

Mounting, removing and wiring of control panel

The control panel is wired straight from the electrical connection box. The control panel can

also be connected in series with a CO

2

 sensor or another control panel. (See External

electrical connections on page 8).

Control panel addresses

If two or more control panels are connected to the system, the addresses of the control panels

need to be changed.

E.g. 3 control panels.

• Connect the first control panel to the unit and change its address to 3.

• Connect the second control panel to the unit and change its address to 2.

• Connect the third control panel and make sure that its address is 1.

If control panels have the same address, they go to bus fault state. In this case, remove one of the control panels
and change the address of the other panel. The above mentioned situation can arise in connection with the later
installation of an additional control panel.

Control panel

Surface mounting
of control panel

A control panel is mounted
on the wall or on a 1-part
instrument box.

Wiring

Width

90 mm

Height

110 mm

Depth

23 mm

Electronics board of control panel

1 = orange 1

= +

2 = white 1

= –

3 = orange 2

= A

4 = white 2

= B

5 = metal

= signal ground

ca. 21 VDC

}

Cable:
NOMAK 2 x 2 x 0.5 mm

2

 + 0.5 mm

2

NOTE!

Faulty coupling of the (+) wire
destroys the control  panel!

1 2 3 4 5
+ – A B  M

© VALLOX • We reserve the right to make changes without prior notification.

VALLOX DIGIT SED CONTROL PANEL

5

Содержание Digit 2 SE Series

Страница 1: ...Preheating unit MLV liquid radiator Post heating unit Electric 1200 W 5 2 A Filters Supply air G3 and F7 Extract air G3 Weight 71 kg Ventilation Control panel control adjustment options Week clock co...

Страница 2: ...panel CO2 sensor option LON converter option Air flow measuring outlets behind cover plate Water radiator actuator valve Connection 12 MLV connection 10 cu 20 21 Supply air to the dwelling Extract air...

Страница 3: ...plate You can measure the total pressure of the supply and extract air ductwork at the measurement outlets using a pressure gauge Compare the pressure readings with the air volume curves to see unit a...

Страница 4: ...7 38 9 31 5 68 0 50 1 66 3 62 9 55 4 46 7 45 0 42 3 34 4 24 3 68 2 52 5 64 1 63 4 59 9 48 7 46 8 45 0 37 1 26 5 69 1 54 2 70 2 65 2 60 0 50 6 48 1 47 1 39 2 32 5 71 8 56 1 70 4 66 9 62 2 52 9 50 2 49...

Страница 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Страница 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Страница 7: ...dB LWA dB A 1 16 24 2 25 47 3 36 70 4 48 90 5 58 104 6 68 116 7 75 131 8 87 148 1 25 7 2 38 7 3 46 46 4 59 69 5 72 79 6 82 106 7 92 112 8 104 141 LpA dB A AP qV dm3 s AP supply extract dm3 s ED and SD...

Страница 8: ...WITCH REMOTE MONITORING 1 10 2 3 4 5 6 7 8 9 1 10 16x0 25mm2 1 2 A 2 3 4 REMOTEMONITORING 0 10VDCor0 20mA ha ro L 6 7 FIREPLACESWITCH 6 va vi va ke R ke r r vi 7 5 7018800 2 1 N K K 1 2 r s m r 2N 1 2...

Страница 9: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Страница 10: ...e loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa...

Страница 11: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Страница 12: ...out prior notification CONTROL DIAGRAM ELECTRIC RADIATOR 12 Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor Exhaust air temperature Standard HR antifreeze Adjustment range 6...

Страница 13: ...henever outdoor air temperature falls below the threshold set or when outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of preheatin...

Страница 14: ...reserve the right to make changes without prior notification CONTROL DIAGRAM VKL MODEL 14 Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor Exhaust air temperature Standard H...

Страница 15: ...e sensors TE1 and TE3 preventing the risk of freezing and the intermittent stopping of supply air fan S If the power of preheating unit R2 is not enough or is not on the control centre intermittently...

Страница 16: ...TION PANEL PLUG LON CONVERTER REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT VENTILATION ZONE INTERNAL ELECTRICAL AND CONTROL CONNECTIONS POST HEA...

Страница 17: ...sensor Automatic Adjustment range 1 99 99 Option Humidity control Adjustment interval 1 15 min 10 10 VALLOX We reserve the right to make changes without prior notification 17 PART LIST Parts list VAL...

Страница 18: ...very antifreeze Controlling preheating in a liquid circulating MLV radiator is different from that in an electric preheating radiator The liquid radiator switches on based on the measurement data from...

Страница 19: ...straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate Installation Lift the unit straight upwards till the locking wings on the sid...

Страница 20: ...ivery Because of the risk of condensing the pump should be suitable for pumping liquid colder than the ambient temperature e g Grundfors UPS 25 60 180 model K MV Solenoid valve not included in the del...

Отзывы: