background image

VALLOX DIGIT2 SE/VKL/MLV

© VALLOX • We reserve the right to make changes without prior notification.

15

DESCRIPTION OF OPERATION/VKL MODEL

Control of operation

Power supply to the unit can be controlled with a contactor in the
distribution panel if needed, e.g. with a timer programme.  After
starting, the unit first operates at minimum power. After that power is
adjusted based either on the measurement data from air quality sensors
and/or on manual control at the control panel.

Fan speed adjustment

Manual control

Fan speed of the ventilation unit is controlled in 8 steps at control
panel 

H

.

Week-clock control

Fan speed of the ventilation unit is controlled in 8 steps using the week
clock in control panel 

H

. The week clock can be used to programme

the desired fan power option and the setpoint for supply air temperature
for each day of the week and each hour in the day.

Carbon dioxide and humidity control

The fan capacity of the ventilation unit is controlled in multiple steps
depending on loads, and based on the measurement results of the air
quality sensors (CO

2

 and %RH sensors) located in the ventilation zone.

 The aim is to keep carbon dioxide and/or humidity content below
the threshold set at control panel 

H

. It is also possible to select an

automatic search for the humidity content setpoint at control panel 

H

.

One or more modes of control may be used simultaneously – the mode
demanding boosting is the dominant one. Fan speed varies depending
on load between the base and maximum fan speeds. The base and
maximum fan speeds can be set at the desired level on control panel

H

.

Control through voltage or current signal

The fan power of the ventilation unit is controlled in 8 steps with a
voltage signal of 0...10 VDC, or with a current signal of 0...20 mA.
However, fan power cannot be raised above the set maximum fan
speed.  Voltage or current signal control is used to control base fan
speed. This means that fan speed can be raised when necessary, but
not lowered, by the manual, CO

2

 and %RH controls.

Supply air temperature

Supply air temperature can be controlled with either constant temperature
control or cascade control.

Constant temperature control of supply air

The control unit directs the operation of post-heating unit 

R1

 on the

basis of the measuring data given by temperature sensor 

TE2

, aiming

at keeping supply air temperature at the temperature value (+10...+30

°

C) set at control panel 

H

.

Cascade control of supply air

The control unit directs the operation of post-heating unit 

R1 

on the

basis of the measuring data given by extract air temperature sensor

TE4

, aiming at keeping supply air temperature at the temperature value

(+10...+30 

°

C) set at control panel 

H

.

Heat recovery bypass

Heat recovery is active whenever post-heating is switched on. Automatic
heat recovery bypass is active when post-heating is switched off and
outdoor air temperature exceeds the threshold set (to bet set in the
range of 0... +25 

°

C). The control centre then controls the operation

of damper motor 

PM

 on the basis of the measurement data given by

outdoor air sensor 

TE3

 and extract air temperature sensor 

TE4

 in order

to get as cool supply air as possible in the ventilation zone. However,
heat recovery is active whenever outdoor air temperature falls below
the threshold set, or when outdoor air is warmer than extract air.

Heat recovery antifreeze

The control centre of the unit controls the operation of preheating unit

R2

 on the basis of the measurement data given by temperature sensors

TE1

 and 

TE3

, preventing the risk of freezing and the intermittent stopping

of supply air fan 

S

. If the power of preheating unit 

R2

 is not enough

or is not on, the control centre intermittently stops supply air fan 

S

 on

the basis of the measurement data given by temperature sensors 

TE1

and 

TE3

, preventing the 

HR

 cell from freezing. As soon as the risk

passes, the fan restarts automatically. The threshold temperature for
antifreeze (-6...+ 15 

°

C) and the difference area (1...10 

°

C) can be

set at control panel 

H

. When fan 

T

 stops, power supply from radiator

R2

 stops and post-heating radiator 

R1

 continues to heat.

For preheating to work, its threshold temperature has to be set by at
least one degree higher than the threshold temperature controlling the
stopping of the fan. Temperatures are adjusted at control panel 

H

.

Overheat protection for the heating unit

Overheat protection thermostats 

TS3

 and 

TS4

 monitor the surface

temperature of heating unit 

R2

. If surface temperature exceeds the

threshold, the overheat protector trips and power supply to the heating
unit is stopped. Overheat protector 

TS3

 is reset automatically, whereas

overheat protector 

TS4

 is reset manually.

Water radiator freezing protection

The control centre of the unit stops fans 

S

 and 

E

, valve 

V

 remains open

and self-actuated dampers 

SP

 close based on the measurement data

given by outdoor air temperature sensor 

TE3

 (outdoor air < 0 

°

C) and

supply air temperature sensor 

TE2

 (supply air < 7 

°

C), reducing the risk

of water heating unit 

R1

 freezing. A freezing alert appears in the

display of the control panel. The fans restart automatically and dampers

SP

 open as soon as the risk of freezing passes (supply air > 10 

°

C).

Alarms

Pressure difference switches 

P1

 and 

P2

 monitor pressure difference on

the supply and extract air sides. If the pressure difference rises too
high because of dirty filters or clogged ducts, an alarm will be issued.
This is indicated by a symbol ( ) in the main display of the control
panel. If the unit is not equipped with pressure difference switches,
the symbol ( ) appearing in the main display of the control panel
reminds of the need of servicing the unit. The reminder interval can
be set at 1...15 months. The factory setting is 4 months. This function
is always active. The fault signal relay in the unit gives potential-free
alarm indications on the following fault conditions:
• When the antifreeze function of the water-circulating radiator is on,

the contacts of the relay close and open at a 10-second interval.

• Alarm of high carbon dioxide content (> 5000 ppm) switches the

relay at 1-second intervals.

• In other fault situations, such as sensor faults, the contacts of the

relay close.

Booster or fireplace switch function

The booster or fireplace switch function of the ventilation unit is controlled
either at control panel 

H

 and/or separate switch 

S

, which can be

connected to the connection box of the unit. The mode of operation
of the switch is selected at control panel 

H

. The booster switch function

raises fan speed to the set maximum fan speed for 45 minutes. The
fireplace switch stops the extract air fan for 15 minutes and produces
overpressure in the ventilation zone. LON remote monitoring control
can be implemented with a VALLOX LON converter. (See a separate
brochure.)

Voltage values
for each fan speed:

0

0.20...1.25 VDC

1

1.75...2.25 VDC

2 2.75...3.25 VDC

3 3.75...4.25 VDC

4 4.75...5.25 VDC

5 5.75...6.25 VDC

6 6.75...7.25 

 

VDC

7.75...8.25    VDC

8 8.75...10.00 

VDC

Current signal values
for each fan speed:

0 0.5...2.5  mA

1

3.5...4.5 mA

2

5.5...6.5 mA

3 7.5...8.5  mA

4 9.5...10.5 mA

5 11.5...12.5 

mA

6 13.5...14.5 

mA

7 15.5...16.5 

mA

8 17.5...20.0 

mA

Voltage and current signal values (selection in the motherboard)

Содержание Digit 2 SE Series

Страница 1: ...Preheating unit MLV liquid radiator Post heating unit Electric 1200 W 5 2 A Filters Supply air G3 and F7 Extract air G3 Weight 71 kg Ventilation Control panel control adjustment options Week clock co...

Страница 2: ...panel CO2 sensor option LON converter option Air flow measuring outlets behind cover plate Water radiator actuator valve Connection 12 MLV connection 10 cu 20 21 Supply air to the dwelling Extract air...

Страница 3: ...plate You can measure the total pressure of the supply and extract air ductwork at the measurement outlets using a pressure gauge Compare the pressure readings with the air volume curves to see unit a...

Страница 4: ...7 38 9 31 5 68 0 50 1 66 3 62 9 55 4 46 7 45 0 42 3 34 4 24 3 68 2 52 5 64 1 63 4 59 9 48 7 46 8 45 0 37 1 26 5 69 1 54 2 70 2 65 2 60 0 50 6 48 1 47 1 39 2 32 5 71 8 56 1 70 4 66 9 62 2 52 9 50 2 49...

Страница 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Страница 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Страница 7: ...dB LWA dB A 1 16 24 2 25 47 3 36 70 4 48 90 5 58 104 6 68 116 7 75 131 8 87 148 1 25 7 2 38 7 3 46 46 4 59 69 5 72 79 6 82 106 7 92 112 8 104 141 LpA dB A AP qV dm3 s AP supply extract dm3 s ED and SD...

Страница 8: ...WITCH REMOTE MONITORING 1 10 2 3 4 5 6 7 8 9 1 10 16x0 25mm2 1 2 A 2 3 4 REMOTEMONITORING 0 10VDCor0 20mA ha ro L 6 7 FIREPLACESWITCH 6 va vi va ke R ke r r vi 7 5 7018800 2 1 N K K 1 2 r s m r 2N 1 2...

Страница 9: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Страница 10: ...e loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa...

Страница 11: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Страница 12: ...out prior notification CONTROL DIAGRAM ELECTRIC RADIATOR 12 Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor Exhaust air temperature Standard HR antifreeze Adjustment range 6...

Страница 13: ...henever outdoor air temperature falls below the threshold set or when outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of preheatin...

Страница 14: ...reserve the right to make changes without prior notification CONTROL DIAGRAM VKL MODEL 14 Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor Exhaust air temperature Standard H...

Страница 15: ...e sensors TE1 and TE3 preventing the risk of freezing and the intermittent stopping of supply air fan S If the power of preheating unit R2 is not enough or is not on the control centre intermittently...

Страница 16: ...TION PANEL PLUG LON CONVERTER REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY ALARM OPERATION MODE CONTROL MEASUREMENT ADJUSTMENT VENTILATION ZONE INTERNAL ELECTRICAL AND CONTROL CONNECTIONS POST HEA...

Страница 17: ...sensor Automatic Adjustment range 1 99 99 Option Humidity control Adjustment interval 1 15 min 10 10 VALLOX We reserve the right to make changes without prior notification 17 PART LIST Parts list VAL...

Страница 18: ...very antifreeze Controlling preheating in a liquid circulating MLV radiator is different from that in an electric preheating radiator The liquid radiator switches on based on the measurement data from...

Страница 19: ...straight The outdoor air duct must be insulated against condensation also between the unit and the ceiling mounting plate Installation Lift the unit straight upwards till the locking wings on the sid...

Страница 20: ...ivery Because of the risk of condensing the pump should be suitable for pumping liquid colder than the ambient temperature e g Grundfors UPS 25 60 180 model K MV Solenoid valve not included in the del...

Отзывы: