MEASURING AND ADJUSTING PERFORMANCE VALUES

Standard ventilation 

The volume flow rate of the air inside the cooker hood is 

measured with the damper closed and, where required, 

adjusted based on the static pressure loss and the 

performance scheme of the cooker hood. 

•  Measure the static pressure loss of the cooker hood by 

pushing the probe through the hole in the damper (see 

the figure). 

•  Determine the volume flow rate from the performance 

scheme based on the measured pressure and the 

number of open holes in the damper. 

Adjustment:

•  Cover the required number of holes in the damper with 

the magnetic strip that is delivered with the cooker 

hood.

dp

dp

>2 x ø

ø

Boost ventilation

The volume flow rate of the air inside the cooker hood 

is measured with the damper open based on the 

static pressure loss and the performance scheme of 

the cooker hood. 

•  Measure the static pressure loss of the cooker hood. 

The measuring point must be located 2 times the 

duct diameter above the outlet collar of the cooker 

hood (see figure).

•  Determine the volume air flow based on the 

measured pressure and the performance scheme 

(with the damper open).

MANU

AL

5

6

7

8

15

20

30

40

50

60 70

10

20

30

40

50

60

70

80

90

200

250

300

400

500

10

100

Measured pressure with a probe P

a without a grease filter

Air flow dm³/s

4

3

2

5 6 7 8

Measured pressure with standard ventilation

Damper open

Adjustment position

L

pA,

bB(A)

K VALUES

Adjustment 

position

Holes of 

the damper 

open

K value

2

2

0,5

3

3

0,6

4

4

0,8

5

5

1,0

6

6

1,1

7

7

1,3

8

8

1,4

Damper open

4,9

  S

TAND

ARD VENTILA

TION

Содержание Delico PTD EC

Страница 1: ...pe A279843 1 Vallox DelicoPTD EC The Vallox Delico PTD EC control hood is suited to controlling EC roof fans and Vallox ventilation units The cooker hood is designed to be used above the cooker top as...

Страница 2: ...the light switch The light is dimmable Adjust the brightness by pressing the light switch until the brightness is adequate Ventilation modes Select the ventilation mode by pressing the ventilation mo...

Страница 3: ...lation unit turns off and the damper closes If this kind of alarm is noticed before fire damage it can be acknowledged by pressing any of the cooker hood buttons Pre selection of light brightness To m...

Страница 4: ...ooker fan must be easy to access CAUTION The cooker hood must not be connected to a flue that is used for removing combustion gases e g from a wood or gas burning fireplace cooker or stove CAUTION Reg...

Страница 5: ...RD FUNCTION NORMAL SITUATION OPEN ACTIVATED CLOSED HOUSE AUTOMATION NORMAL SITUATION OPEN ERROR SITUATION HOOD OR VENTILATION UNIT CLOSED ACTIVATED GUARD FUNCTION FLASHING POSITION OF THE DAMPER DAMPE...

Страница 6: ...mum voltage of 10 VDC Next press the ventilation mode button which sets the control voltage at 2 5 VDC After this the voltage will increase by 0 5 VDC at a time Save the selected control voltage by pr...

Страница 7: ...dp dp 2 x Boost ventilation The volume flow rate of the air inside the cooker hood is measured with the damper open based on the static pressure loss and the performance scheme of the cooker hood Meas...

Страница 8: ...Vallox DelicoPTD EC D9517 18 12 2020 www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Technical support 358 10 7732 270...

Отзывы: