As the default factory setting, the Vallox Delico PTD EC 

cooker hood has the following fan control voltages:

Away: 2.5 VDC | At home: 5.0 VDC | Boost: 7.5 VDC

To adjust the control voltage:

•  Close the damper, turn off the lights, and select  

the At home ventilation profile.

•  Press the selection button for roughly 3 seconds 

until the setting mode signal light starts to flash. 

The signal light will flash in a series of five flashes 

to indicate that the 5 VDC control voltage is set.

•  Press the ventilation mode button. The signal light 

will flash in a series of five one quick 

flashes (5.5 VDC).

•  Press the ventilation mode button. The signal light 

will flash in a series of six flashes (6.0 VDC).

•  Press the ventilation mode button. The signal 

light will flash in a series of six one quick 

flashes (6.5 VDC).  

•  Keep on pressing until you reach the maximum 

voltage of 10 VDC. Next, press the ventilation 

mode button, which sets the control voltage at 2.5 

VDC. After this, the voltage will increase by 0.5 

VDC at a time.

•  Save the selected control voltage by pressing the 

selection button until the signal lights flash. Saving 

the fan speed of the At home mode also adjusts 

and saves the efficiency of the Away and Boost 

modes.

•  The efficiency of the Away and Boost modes can 

also be adjusted separately. In this case, adjusting 

only affects the mode that is selected. The mode 

that is to be adjusted needs to be selected when 

moving to the setting mode.

•  Alternatively, the control voltage can be controlled 

using a general meter. For that purpose, there are 

probes at the bottom of the filter enclosure (see 

figure).

SETTING VENTILATION MODES

5

6

7

8

15

20

30

40

50

60 70

10

20

30

40

50

60

70

80

90

200

250

300

400

500

10

100

Total pressure Pa

Air flow dm³/s

L

pA,

bB(A)

25

30

35

40

45

30

4

3

2

5

6

7 8

Adjustment position 

Total pressure loss  

with boost ventilation 

35

Total pressure loss with standard ventilation (damper closed)

(damper open)

Содержание Delico PTD EC

Страница 1: ...pe A279843 1 Vallox DelicoPTD EC The Vallox Delico PTD EC control hood is suited to controlling EC roof fans and Vallox ventilation units The cooker hood is designed to be used above the cooker top as...

Страница 2: ...the light switch The light is dimmable Adjust the brightness by pressing the light switch until the brightness is adequate Ventilation modes Select the ventilation mode by pressing the ventilation mo...

Страница 3: ...lation unit turns off and the damper closes If this kind of alarm is noticed before fire damage it can be acknowledged by pressing any of the cooker hood buttons Pre selection of light brightness To m...

Страница 4: ...ooker fan must be easy to access CAUTION The cooker hood must not be connected to a flue that is used for removing combustion gases e g from a wood or gas burning fireplace cooker or stove CAUTION Reg...

Страница 5: ...RD FUNCTION NORMAL SITUATION OPEN ACTIVATED CLOSED HOUSE AUTOMATION NORMAL SITUATION OPEN ERROR SITUATION HOOD OR VENTILATION UNIT CLOSED ACTIVATED GUARD FUNCTION FLASHING POSITION OF THE DAMPER DAMPE...

Страница 6: ...mum voltage of 10 VDC Next press the ventilation mode button which sets the control voltage at 2 5 VDC After this the voltage will increase by 0 5 VDC at a time Save the selected control voltage by pr...

Страница 7: ...dp dp 2 x Boost ventilation The volume flow rate of the air inside the cooker hood is measured with the damper open based on the static pressure loss and the performance scheme of the cooker hood Meas...

Страница 8: ...Vallox DelicoPTD EC D9517 18 12 2020 www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Technical support 358 10 7732 270...

Отзывы: