MOUNTING INSTRUCTIONS

Ceiling mounting/

ceiling mounting plate

Fastening of ceiling mounting plate to ceiling. 

The ceiling mounting plate is mounted straight, 

and it has to be fastened so that there is a 

space of circa 6 mm between the back edge 

of the ceiling mounting plate and the wall 

(Figure 1). The ventilation unit then becomes 

attached to the back wall. Minimum distance 

between the bottom edge of the ceiling 

mounting plate and the ceiling of the room 

is 14 mm. With this distance, there will be a 

vent of circa 2 mm between the top edge of 

the mounted unit and the ceiling.
The ceiling mounting plate is fi xed to the 

ceiling with M8 thread bars. After the thread 

bars have been fastened to the ceiling, fi rst 

turn the nuts into the thread bars and lift the 

ceiling mounting plate in place. Then push a 

rubber damper and washer to each thread 

bar, all the way into the cup of the plate, and 

turn the nut. Shorten the lower ends of the 

thread bars so that they will be at no more 

than 25 mm from the lower surface of the 

ceiling mounting plate. NOTE! Shortening 

the thread bars can only be done before 

mounting the ceiling mounting plate. The 

maximum length of a thread bar from the 

lower surface of the ceiling is the space 

between the lower surface of the ceiling and 

the lower surface of the ceiling mounting 

plate + 25 mm.

Mounting of ventilation unit 

to ceiling mounting plate

Before lifting the unit to the ceiling mounting plate, detach the front panel 

from the unit (and leave it hang from the measurement hoses), Figure 2:
Put the cables of the connection box into the slot in the upper part of the 

side plate and pull the connection box next to the unit so that the cables 

remain in the slot. Make sure that the duct outlets for the unit’s extract air 

duct and for the duct coming from the outside to the unit are equipped with 

condensing water insulation. Lift the unit in place to the ceiling mounting 

plate till both locking wings lock to the outer edge of the side plate of the 

unit. Do a visual check of the tightness of the duct outlets and of the correct 

moving of the measurement hoses and electric cables. Fasten the front panel 

back in place.

Air fl ow measurement outlets

The fi xed measurement outlets are located behind the nameplate. You can 

measure the total pressure of the supply and extract air ductwork at the me-

asurement outlets, using a differential pressure instrument. Pressure readings 

and air volume tables show volume fl ow rates at various adjustment posi-

tions. The red measurement hose is on the pressure side and the black hose 

on the suction side of the fan.

Figure   1

Nuts 

Rubber damper

Lower surface of ceiling

Washer

ceiling

wall

Figure 2

Locking wing

Содержание 90MC Series

Страница 1: ...LOX 90MC L Operating maintenance and technical instructions 10 1 2 8 4 5 3 11 12 6 7 9 Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP34 Fans Extract air 0 119 k...

Страница 2: ...r fan during the time when the fireplace is lighted NOTE The starting of the extract air fan may weaken draught in the fireplace In winter this situation may disturb the winter function of the unit Th...

Страница 3: ...he unit with two kinds of filters A coarse filter A filters off insects heavy pollen and other dust An F7 class fine filter B filters off fine dust invisible to the eye Extract air is filtered with a...

Страница 4: ...y disconnect the quick coupling of the fan conductor Detaching extract air filter B The fan is attached to the fixing plate with a butter y nut Detach the butter y nuts and lift the fan out Finally di...

Страница 5: ...m3 s At a lower total pressure SFP will be smaller at this speed Sound values Sound power level from the ventilation unit to supply air ducts by octave band LW dB Sound power level from the ventilatio...

Страница 6: ...Fault signal relay output 7023000 TECHNICAL DATA 1 2 3 4 5 6 7 8 9 1 2 3 4 5 LINE NEUTRAL SLI SNI SLO SNO SFL SFN EFL EFN FSO FSI AHL AHN PHL PHN 230V 50Hz BL1 BL BN E I E O 12 34 LED 90 C 130 C R1 T...

Страница 7: ...onstruction during mounting Avoid mounting the unit on a hollow echoing dividing wall and on a bedroom wall because of sound conduction or prevent sound conduction Condensing water The delivery includ...

Страница 8: ...a thread bar from the lower surface of the ceiling is the space between the lower surface of the ceiling and the lower surface of the ceiling mounting plate 25 mm Mounting of ventilation unit to ceil...

Отзывы: