MAINTENANCE INSTRUCTIONS

Fans

Check the cleanliness of the fans when carrying out maintenance 

for a fi lter and the heat recovery cell. Clean the fans if needed. The 

fans can be removed from the unit for cleaning. The fan blades can 

be cleaned with compressed air or with a brush. Do not remove or 

move the balancing pieces on the fan blade.

Detaching supply air fi lter (A)

Before detaching the supply air fan, you must remove the F7 fi ne fi lter 

(C). To remove the F7 fi ne fi lter, pull it out. The fan is attached to the 

fi xing plate with a butterfl y nut. Detach the butterfl y nuts and lift the 

fan off. Finally, disconnect the quick coupling of the fan conductor.

Detaching extract air fi lter (B)

The fan is attached to the fi xing plate with a butterfl y nut. Detach 

the butterfl y nuts and lift the fan out. Finally, disconnect the quick 

coupling of the fan conductor. If you use water for cleaning the unit 

or parts of it, do not let it enter the electrical parts.

Condensing water

During the heating season, humidity of extract air condenses into 

condensing water. Water formation may be abundant in new 

buildings or if ventilation is low compared to the humidity build-up 

caused by the residents. Condensing water needs to fl ow out from 

the ventilation unit without hindrance. In carrying out maintenance, 

e.g. in autumn before the beginning of the heating season, make 

sure that the condensing water outlet (L) in the bottom tank is not 

clogged. You can check it by pouring a little water in the tank. Clean 

if needed. Do not let water fl ow into electrical devices.

Содержание 90MC Series

Страница 1: ...LOX 90MC L Operating maintenance and technical instructions 10 1 2 8 4 5 3 11 12 6 7 9 Electrical connection 230 V 50 Hz 5 7 A Degree of protection provided by enclosures IP34 Fans Extract air 0 119 k...

Страница 2: ...r fan during the time when the fireplace is lighted NOTE The starting of the extract air fan may weaken draught in the fireplace In winter this situation may disturb the winter function of the unit Th...

Страница 3: ...he unit with two kinds of filters A coarse filter A filters off insects heavy pollen and other dust An F7 class fine filter B filters off fine dust invisible to the eye Extract air is filtered with a...

Страница 4: ...y disconnect the quick coupling of the fan conductor Detaching extract air filter B The fan is attached to the fixing plate with a butter y nut Detach the butter y nuts and lift the fan out Finally di...

Страница 5: ...m3 s At a lower total pressure SFP will be smaller at this speed Sound values Sound power level from the ventilation unit to supply air ducts by octave band LW dB Sound power level from the ventilatio...

Страница 6: ...Fault signal relay output 7023000 TECHNICAL DATA 1 2 3 4 5 6 7 8 9 1 2 3 4 5 LINE NEUTRAL SLI SNI SLO SNO SFL SFN EFL EFN FSO FSI AHL AHN PHL PHN 230V 50Hz BL1 BL BN E I E O 12 34 LED 90 C 130 C R1 T...

Страница 7: ...onstruction during mounting Avoid mounting the unit on a hollow echoing dividing wall and on a bedroom wall because of sound conduction or prevent sound conduction Condensing water The delivery includ...

Страница 8: ...a thread bar from the lower surface of the ceiling is the space between the lower surface of the ceiling and the lower surface of the ceiling mounting plate 25 mm Mounting of ventilation unit to ceil...

Отзывы: