VALLOX 252 D

5

INSTRUCTIONS FOR USE

Control panel

Service reminder

• The maintenance reminder switches on the maintenance reminder symbol ( ) in

the control panel at defined intervals, the factory setting being 4 months.

• The maintenance reminder symbol is acknowledged at the main display of the

control panel (see the instructions for using the control panel, Section 1.3.7.).

• The interval may be set between 1 and 15 months on the control panel.

Supply air constant temperature control

• The basic setting for supply air temperature control is constant temperature

control.

• The aim is to permanently keep the temperature of air blown to the ventilation

zone within the range +10...+30˚C.

• Temperature control is only active when post-heating has been switched on.

Supply air cascade control

• Supply air temperature control can be replaced with cascade control.

• Cascade control changes the mode of regulating the post-heating radiator: the

temperature of air blown to the ventilation zone is controlled on the basis of
extract air.

• Temperature is controlled on the basis of the difference between the setpoint and

the actual temperature. For instance, if indoor air temperature is 25˚C and the
setpoint is 24˚C, the aim is to blow 23˚C air to the ventilation zone. If the
temperature in the ventilation zone is 24˚C and the setpoint is 25˚C, the aim is to
blow 26˚C air to the ventilation zone.

• The aim is to permanently keep the temperature of air blown to the ventilation

zone within the range +10...+30˚C.

• Cascade control can be chosen on the control panel, and it is active when post-

heating has been switched on.

Fireplace switch / boosting function

• The booster switch raises fan speed to the preset maximum fan speed for 45

minutes.

• The fireplace switch stops the extract air fan for 15 minutes and causes

overpressure in the ventilation zone. This facilitates lighting up the fireplace, for
instance.

NOTE! When the extract air fan starts, the draft in the fireplace may stop.

• The function is selected on the control panel.

Fault signalling relay

• The fault signalling relay has potential free points (24VDC, 1A).

• The points provide information on failure modes of the ventilation unit.

• During water radiator defrosting, the points of the relay close and open at 10-

second intervals.

• High carbon dioxide content alarm switches the relay every second.

• In other failure situations, the points are closed.

Содержание 252 D Series

Страница 1: ...0 W 1 A 2x230 W 1 A Fans Heat recovery Heat recovery bypass Preheater Electric post heating unit Water circulated post heating unit Filters Filters Manual control DIGIT control panel CO2 and RH contro...

Страница 2: ...goes under the preset threshold value To avoid or to decrease the stopping of the supply air fans you can heat outdoor air with an electric preheater If the unit is equipped with a preheater defrostin...

Страница 3: ...djusts fan speed so as to keep the carbon dioxide content in the ventilation zone below the setpoint If two or more sensors are used fan speed is adjusted in accordance with the highest measuring resu...

Страница 4: ...0 25 C The factory setting is 10 C Heat recovery cell defrosting function The defrosting function prevents the heat recovery cell from freezing thereby ensuring that ventilation works in cold periods...

Страница 5: ...setpoint and the actual temperature For instance if indoor air temperature is 25 C and the setpoint is 24 C the aim is to blow 23 C air to the ventilation zone If the temperature in the ventilation zo...

Страница 6: ...tings menu press the and buttons simultaneously In the settings menu you can change setpoints for the ventilation unit The content display shows humidity and carbon dioxide content The corresponding s...

Страница 7: ...he control panel is changed with the and buttons Two control panels cannot have the same address If control panels have the same address they will go to the bus fault state and will not operate The de...

Страница 8: ...may cause a faulty post heating function 1 3 17 Choosing post heating for the unit Radiator type electric rad Automatic or manual search of the basic humidity level The selection is done with the and...

Страница 9: ...1 3 22 Changing the setpoint for carbon dioxide adjustment CO2 setting 0900 PPM Basic fan speed 1 Maximum fan speed 8 Carbon dioxide adjustment CO2 900 ppm CO2 Basic humidity level value chosen eithe...

Страница 10: ...he doors of the ventilation unit have to be mounted 5 If the filter guard symbol appears in the main display of the control panel proceed to step 7 If it does not appear proceed to step 6 6 You can in...

Страница 11: ...is not functioning The extract air filter or the cell is clogged The initial adjustments for ventilation have not been made 1 Check the insulation of the attic ducts If the heat recovery cell has fro...

Страница 12: ...e but they can be cleaned with pressure air carefully blowing against the direction of contamination When needed replace the filters with new ones The recommended interval for filter change is one yea...

Отзывы: