VALLOX 252 D

4

INSTRUCTIONS FOR USE

Pressure difference switch

LON converter

Ventilation control with voltage or current signals

• The fan speeds of VALLOX 252 D can be controlled with voltage or current signals

coming from the remote monitoring system.

• The signal can be used to select speeds 0...8. However, the maximum fan speed may not

be exceeded, if carbon dioxide or humidity control is active.

• The signal changes the basic fan speed.

• The signal does not lock the fan speed, i.e. it can be changed on the control panel within

the defined range. Carbon dioxide and humidity controls also operate within the defined
range.

Ventilation control with remote monitoring system

• With the help of an optional LON converter, VALLOX 252 D can be connected to a

remote monitoring system.

• Before connecting VALLOX 252 D to the remote monitoring system, make sure that they

are compatible.

• The remote monitoring system may be used to control the same functions that can be

controlled on the control panel.

• The remote monitoring system works in parallel with the control panel and the carbon

dioxide and humidity sensors.

Heat recovery bypass

• The aim of the heat recovery bypass function is to ensure that supply air coming to the

ventilation zone is as cool as possible. To do this, the heat recovery bypass function
compares the measurement data of the outdoor and extract air sensors.

• The heat recovery cell is bypassed when the post-heating function is off and outdoor air

temperature exceeds the setpoint.

• Heat recovery is active whenever outdoor temperature is two degrees below the setpoint.

• The setpoint may be changed within the range 0˚...+25˚C. (The factory setting is 10˚C.)

Heat recovery cell defrosting function

• The defrosting function prevents the heat recovery cell from freezing, thereby ensuring

that ventilation works in cold periods, too.

• The defrosting function uses preheating and, when needed, stops the supply air fan on

the basis of the measurement data received from the temperature sensor that detects the
temperature of exhaust air after the heat recovery cell. When the risk of freezing passes,
preheating will be switched off and the supply air fan will start automatically.

• The preheating activation temperature of the defrosting function (factory s3˚C),

the temperature for stopping the supply air fan (factory s1˚C) and the operating
temperature hysteresis (factory setting 1˚C) can be set on the control panel.

Defrosting of water circulated post-heating unit

• The defrosting function aims at preventing the water circulated post-heating unit from

freezing. The automatic function stops the supply and extract air fans of the ventilation
unit whenever outdoor temperature descends below 0˚C and supply air temperature
goes below +7˚C, in which case the control valve becomes wide open and the message
FREEZING ALERT shows in the control panel display. The function opens and closes the
points of the fault signalling relay at 10-second intervals.

• The fans start automatically as soon as supply air temperature exceeds 10˚C.

Filter guard function

• If VALLOX 252 D is equipped with a pressure difference switch for the supply and/or

extract air ductwork, the switch monitors the pressure difference in the whole ductwork.
When pressure has risen (e.g. because of a clogged filter), the filter guard indicator ( ) in
the main display of the control panel lights up.

• When the lamp is lit, the filter guard closes the points of the fault signalling relay.

Содержание 252 D Series

Страница 1: ...0 W 1 A 2x230 W 1 A Fans Heat recovery Heat recovery bypass Preheater Electric post heating unit Water circulated post heating unit Filters Filters Manual control DIGIT control panel CO2 and RH contro...

Страница 2: ...goes under the preset threshold value To avoid or to decrease the stopping of the supply air fans you can heat outdoor air with an electric preheater If the unit is equipped with a preheater defrostin...

Страница 3: ...djusts fan speed so as to keep the carbon dioxide content in the ventilation zone below the setpoint If two or more sensors are used fan speed is adjusted in accordance with the highest measuring resu...

Страница 4: ...0 25 C The factory setting is 10 C Heat recovery cell defrosting function The defrosting function prevents the heat recovery cell from freezing thereby ensuring that ventilation works in cold periods...

Страница 5: ...setpoint and the actual temperature For instance if indoor air temperature is 25 C and the setpoint is 24 C the aim is to blow 23 C air to the ventilation zone If the temperature in the ventilation zo...

Страница 6: ...tings menu press the and buttons simultaneously In the settings menu you can change setpoints for the ventilation unit The content display shows humidity and carbon dioxide content The corresponding s...

Страница 7: ...he control panel is changed with the and buttons Two control panels cannot have the same address If control panels have the same address they will go to the bus fault state and will not operate The de...

Страница 8: ...may cause a faulty post heating function 1 3 17 Choosing post heating for the unit Radiator type electric rad Automatic or manual search of the basic humidity level The selection is done with the and...

Страница 9: ...1 3 22 Changing the setpoint for carbon dioxide adjustment CO2 setting 0900 PPM Basic fan speed 1 Maximum fan speed 8 Carbon dioxide adjustment CO2 900 ppm CO2 Basic humidity level value chosen eithe...

Страница 10: ...he doors of the ventilation unit have to be mounted 5 If the filter guard symbol appears in the main display of the control panel proceed to step 7 If it does not appear proceed to step 6 6 You can in...

Страница 11: ...is not functioning The extract air filter or the cell is clogged The initial adjustments for ventilation have not been made 1 Check the insulation of the attic ducts If the heat recovery cell has fro...

Страница 12: ...e but they can be cleaned with pressure air carefully blowing against the direction of contamination When needed replace the filters with new ones The recommended interval for filter change is one yea...

Отзывы: