background image

VALLOX 252 D

11

TROUBLESHOOTING

After a power failure, the unit will start at the basic speed. All the other adjustments and setpoints chosen will remain in the memory of the unit.

SYMPTOM

CAUSE

DO THIS

"Bus fault" message is displayed
and unit runs at fan speed 1.

• There is a wiring fault in the CO

2

 sensor,

huminity sensor or in the control panel.

9

• Contact a service representative. The couplings have to be checked

and repaired if needed.

"Freezing alert" message is
displayed and the unit is
stopped.

• The defrosting of the water circulated

radiator is operating.

NOTE! If there is no anti-freezing agent in the water of
the radiator, there is a risk that the radiator will freeze.

10

• Immediately sort out the situation. Contact your service representative

to find out if there is any anti-freezing agent in the radiator. Check if
the circulating water pump has been broken, if the heating boiler is
out of operation, etc. The situation may pass by itself when supply
air temperature rises above 10˚C, but do not await that.

The desired automatic adjustment
does not stay activated.

• There is a fault in the humidity sensor,

pressure sensor or CO

2

 sensor; one of

the sensors is broken or missing.

11

• Contact a service representative. The mounting and couplings of the

sensors have to be checked. (The sensors are optional.)

The unit does not obey the control
panel.

13

• Remove the plug from the wall outlet, wait for 30 seconds and put it

back. If this does not help, contact a service representative.

"Carbon dioxide alarm!!" message
is displayed and the unit is
stopped.

• CO

2

 alarm. Carbon dioxide content has

exceeded 5000 ppm for more than two
minutes. This may be because of a fire, for
instance.

14

• If there is a fire, take the necessary steps.
• The unit can be brought back to operation by removing the plug from

the wall outlet, waiting for 30 seconds and putting the plug back.

The filter guard symbol ( ) is
displayed and the unit operates
otherwise normally.

• Pressure in the filter guard (pressure

difference switch) has risen above
the setup, or speed is 7 or 8.

15

• Check the cleanliness of the filters and the unit. Clean or replace the

filters, if necessary. Also check the external grille.

• The door switch may be broken or has not

closed properly.

• The socket is dead; the fuse may have

burned out, for instance.

• The glass tube fuse protecting the internal

electronics of the unit (located on the control
board behind the protective plate) may have
burned out.

The unit is deaf, the fans do not
rotate, and none of the indicator
lamps of the control panel is lit.

12

• Check the door switch and the fuses. The unit has a glass tube fuse,

T800mA.

• If needed, contact a service representative (in order to check the

glass tube fuse, for instance).

Outdoor air is cool when entering
the house.

• Air cools down in the attic ducts.
• The heat recovery cell has frozen,

and extract air cannot heat outdoor
air.

• The post-heating radiator is not

functioning.

• The extract air filter or the cell is

clogged.

• The initial adjustments for ventilation

have not been made.

1

• Check the insulation of the attic ducts.
• If the heat recovery cell has frozen, check the defrosting protection

setpoint. You may increase the setpoint by 1 or 2˚C, or you can bend
the sensor closer to the cell, which causes the supply air fan to stop
earlier (see the instructions for using the control panel, Section
1.3.20). Defrost the cell before closing the door.

• If the post-heating radiator does not operate, check to see if

overheating protection prevents it from operating. Press the
overheating protection button, and measure the temperature of supply
air inside the unit when the door is closed. If, even after this, the
radiator does not function, contact a service representative.

• Check the cleanliness of the filters and the heat recovery cell.

The supply air fan keeps stopping.

• Stopping of the supply air fan is

active.

NOTE! If you decrease the threshold by too much,
the cell may freeze. See item 1 on this page.

2

• The fan stops less often and the efficiency of the heat recovery cell is

enhanced if the setpoint is decreased by 1 or 2˚C.
(See the instructions for using the control panel, Section 1.3.20.).

The supply air fan stops and starts
too frequently.

• The difference between the stopping

and starting temperatures is too small.

3

• Increase the difference by 1 or 2˚C, thereby lengthening the interval

between the stopping and starting of the supply air fan. (See the
instructions for using the control panel, Section 1.3.19).

The maintenance reminder symbol (   )
is displayed and the unit operates
otherwise normally.

• The maintenance reminder lights up the

maintenance reminder symbol in the
main display of the control panel at an
interval of approximately 4 months
(factory setting).

• You may change the interval (see the

instructions for using the control panel,
Section 1.3.18.).

4

• Check the cleanliness of the filters and the unit, and clean or replace

the filters if needed. Check the external grille as well.

•  Acknowledge the maintenance reminder symbol to make it

disappear. (See the instructions for using the control panel, Section
1.3.7.).

"Exh. air sensor fault" message is
displayed and the unit is stopped.

• There is a fault in the defrosting

sensor.

5

• Contact a service representative. The sensor mounting has to be

checked, and the sensor has to be replaced if necessary.

"Sup. air sensor fault" message is
displayed and the unit is stopped.

• There is a fault in the supply air

sensor.

6

• Contact a service representative. The sensor mounting has to be

checked, and the sensor has to be replaced if necessary.

"Ind. air sensor fault" message is
displayed and the unit is stopped.

• There is a fault in the extract air

sensor.

7

• Contact a service representative. The sensor mounting has to be

checked, and the sensor has to be replaced if necessary.

"Out air sensor fault" message is
displayed and the unit is stopped.

• There is a fault in the outdoor air

sensor.

8

• Contact a service representative. The sensor mounting has to be

checked, and the sensor has to be replaced if necessary.

Содержание 252 D Series

Страница 1: ...0 W 1 A 2x230 W 1 A Fans Heat recovery Heat recovery bypass Preheater Electric post heating unit Water circulated post heating unit Filters Filters Manual control DIGIT control panel CO2 and RH contro...

Страница 2: ...goes under the preset threshold value To avoid or to decrease the stopping of the supply air fans you can heat outdoor air with an electric preheater If the unit is equipped with a preheater defrostin...

Страница 3: ...djusts fan speed so as to keep the carbon dioxide content in the ventilation zone below the setpoint If two or more sensors are used fan speed is adjusted in accordance with the highest measuring resu...

Страница 4: ...0 25 C The factory setting is 10 C Heat recovery cell defrosting function The defrosting function prevents the heat recovery cell from freezing thereby ensuring that ventilation works in cold periods...

Страница 5: ...setpoint and the actual temperature For instance if indoor air temperature is 25 C and the setpoint is 24 C the aim is to blow 23 C air to the ventilation zone If the temperature in the ventilation zo...

Страница 6: ...tings menu press the and buttons simultaneously In the settings menu you can change setpoints for the ventilation unit The content display shows humidity and carbon dioxide content The corresponding s...

Страница 7: ...he control panel is changed with the and buttons Two control panels cannot have the same address If control panels have the same address they will go to the bus fault state and will not operate The de...

Страница 8: ...may cause a faulty post heating function 1 3 17 Choosing post heating for the unit Radiator type electric rad Automatic or manual search of the basic humidity level The selection is done with the and...

Страница 9: ...1 3 22 Changing the setpoint for carbon dioxide adjustment CO2 setting 0900 PPM Basic fan speed 1 Maximum fan speed 8 Carbon dioxide adjustment CO2 900 ppm CO2 Basic humidity level value chosen eithe...

Страница 10: ...he doors of the ventilation unit have to be mounted 5 If the filter guard symbol appears in the main display of the control panel proceed to step 7 If it does not appear proceed to step 6 6 You can in...

Страница 11: ...is not functioning The extract air filter or the cell is clogged The initial adjustments for ventilation have not been made 1 Check the insulation of the attic ducts If the heat recovery cell has fro...

Страница 12: ...e but they can be cleaned with pressure air carefully blowing against the direction of contamination When needed replace the filters with new ones The recommended interval for filter change is one yea...

Отзывы: