5
380
165
433
The minimum distance between the top of the unit and the
fi nished ceiling surface is 30 mm.
Pipe outer diameter ø 12 mm
Wall mounting plate
Take into account that the unit rises
during mounting 10 mm higher t
han the fi nal height.
Wall mounting plate
Bottom edge of wall bracket
162
12
21
20 60
20 30 30
20
60
11
20
30
30
11
84
84
35 30
35
ø7 14kpl
550
30
25
25
30
ϒ
MOUNTING
Mounting
VALLOX 096 SE has to be mounted in a place where temperature does
not go below +10 °C. Without protective enclosure, the unit must be
located in a place with no acoustic disturbance: storerooms, technical
rooms etc.
Wall mounting
VALLOX 096 SE is mounted on the wall with a mounting plate as shown
in the adjacent fi gure. Make sure that the unit is horizontally level after
mounting.
Wall construction
Observe the wall construction during mounting. Avoid mounting the unit
on a hollow, echoing dividing wall and on a bedroom wall because of
sound conduction, or prevent sound conduction.
Condensing water connections
The delivery includes a water seal. By connecting a pipe to the water
seal the water condensing from extract air can be led to a fl oor drain
(not directly to the drain). The pipe must not rise after the water seal.
The unit has to be mounted horizontally level, so that condensing water
can get freely out of the unit.