MOUNTING
Ceiling mounting with ceiling mounting plate
(option)
An optional ceiling mounting plate can be used with the unit. The cei-
ling mounting plate is fi xed to the ceiling with M8 thread bars. Fix the
bars so that they stand the weight of the unit.
The ceiling mounting plate has to be fi xed horizontally in order to en-
sure that the unit will be straight. The outdoor air and exhaust air duct
must be insulated against condensation also between the unit and the
ceiling mounting plate.
The ceiling mounting plate is mounted horizontally level, and it has to
be attached so that there is a space of circa 4 mm between the back
edge of the ceiling mounting plate and the wall. The ventilation unit is
then as close to the wall as possible. Minimum distance between the
bottom edge of the ceiling mounting plate and the ceiling of the room
is 50 mm.
The ceiling mounting plate is fi xed to the ceiling with M8 thread bars.
After the thread bars have been fastened to the ceiling, fi rst turn the nuts
into the thread bars and lift the ceiling mounting plate in place. Then
4
332
544
600
600
push a rubber damper and washer to each thread bar, all the way into
the cup of the plate, and turn the nut. Shorten the lower ends of the
thread bars so that they will be at no more than 25 mm from the lower
surface of the ceiling mounting plate.
Mounting of ventilation unit to ceiling mounting plate
Mount the locking washers (J) delivered with the ceiling mounting plate
in place with the 4 screws. Lift the unit and take the wires through the
opening in the ceiling mounting plate. Put the locking devices attached
to the top of the ventilation unit at the openings in the ceiling mounting
plate and lift upwards. Make sure that the unit is locked in place.
Check that the condensing water insulation between the unit and the
ceiling mounting plate is in place in the exhaust and outdoor air duct.
The unit can be detached from the ceiling mounting plate by pulling
the spring-loaded moulding to the direction shown by the arrow (more
detailed information provided with the ceiling mounting plate).
5
395
8
15
15
630
Attic fl oor penetration plate
(option)
When an attic fl oor penetration plate is used, the tightness of the vapour barrier has to be ensured.
Ceiling mounting plate
(option)
Minimum distance
to back wall is 5 mm
Minimum distance
to side walls is 15 mm
Minimum distance between bottom edge
of ceiling mounting plate and ceiling of
room 50 mm
Minimum distance to back wall 4 mm
J
Minimum distance 10 mm