MAINTENANCE

Before starting maintenance operations

When you open the VALLOX 096 SE unit, the security switch (S) turns 

voltage off. In spite of this, disconnect the plug of the unit. Disconnect 

the plug of the VALLOX 096 SE unit before starting maintenance 

operations.

Filters

When the maintenance reminder gives an alarm, the cleanliness of the 

fi lters must be checked. Outdoor air is fi ltered in the unit with two kinds 

of fi lters. A coarse fi lter (A) fi lters off insects, heavy pollen and other 

dust. An F7 class fi ne fi lter (B) fi lters off fi ne dust invisible to the eye. 

Extract air is fi ltered with a coarse fi lter (C).
By using original Vallox fi lters you ensure good operation of the 

ventilation unit and the best fi ltering result. The replacement interval 

of fi lters depends on dust content in ambient air. It is recommended to 

replace fans in spring and autumn, but at least once a year.

MAINTENANCE INSTRUCTIONS

Heat recovery cell

When  you  replace  the  fi lters,  you  are  also  advised  to  check  the 

cleanliness of the heat recovery (HR) cell (D) at an interval of 

approximately every two years. The sealing ledge (E) above the HR 

cell must be pulled off in the direction shown by the arrow in the fi gure. 

When the sealing ledge has been removed, the HR cell can be pulled 

out of the unit. Note! The laminas of the HR cell are very thin and get 

easily damaged.
If the HR cell is dirty, wash it by putting it in a solution of water with 

washing-up liquid. Rinse the HR cell clean with a jet of water. When 

water has drained from between the laminas, you can push the HR cell 

back in place. Finally, push the sealing ledge in place.

Содержание 096 SE L

Страница 1: ...erating maintenance and technical instructions Electrical connection 230 V 50 Hz 5 1 A plug Degree of protection provided by enclosures IP 34 Fans Extract air 89 dm3 s 100 Pa direct current DC Supply...

Страница 2: ...ring result 1 to 2 carbon dioxide sensors can be connected as options to the VALLOX 096 SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel Th...

Страница 3: ...heating indicator light Maintenance reminder symbol Maintenance reminder The maintenance reminder switches on the maintenance reminder symbol on the main display of the control panel at defined interv...

Страница 4: ...menu you can change setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on wh...

Страница 5: ...water or electric radiator is selected with the and buttons depending on the type of post heating radiator the unit is equipped with Note Choosing the wrong type of post heating may cause a faulty pos...

Страница 6: ...ttons The rotation speed of the extract air fan can be decreased by decreasing the percentage Move the cursor with the arrow keys and change values with the and buttons Note that to exit and save when...

Страница 7: ...By using original Vallox filters you ensure good operation of the ventilation unit and the best filtering result The replacement interval of filters depends on dust content in ambient air It is recomm...

Страница 8: ...you wish to detach the fan lift it upwards and crank the plastic lock to the right using for instance a chisel gure 6 The fan then falls down and can be pulled out of the unit Disconnect the quick co...

Страница 9: ...t message is displayed and the unit operates at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type C...

Страница 10: ...ing range E Extract air fan S Supply air fan Input power total W Air flow max dm3 s SFP SFP Specific Fan Power recommended value 2 5 kW m3 s At a lower total pressure SFP will be smaller at this speed...

Страница 11: ...P W M 5 4 3 2 1 M 2x0 25 3x0 25 BN WT BN GN connection box on top of the unit 5 3 10 1 FAN CONTROL 0 10 V DC A B M S S 1 2 S S RH1 RH2 RS 485 BUS FAULT SIGNAL FIREPLACE SWITCH 12x0 25mm2 N GND L1 L 1...

Страница 12: ...t state In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional contr...

Страница 13: ...t protective enclosure the unit must be located in a place with no acoustic disturbance storerooms technical rooms etc Wall mounting VALLOX 096 SE is mounted on the wall with a mounting plate as shown...

Страница 14: ...ting plate in place Then 4 332 544 600 600 push a rubber damper and washer to each thread bar all the way into the cup of the plate and turn the nut Shorten the lower ends of the thread bars so that t...

Страница 15: ...l 3467200 10 Filter stand 3464500 No Part Code 11 G4 coarse filter 978045 extract air 12 Bypass duct assembly 3475100 indicate if right or left handed 13 Damper motor 930613 14 Extract air outlet 9850...

Страница 16: ...1 09 602E 3 12 2013 PDF...

Отзывы: