User’s Guide ______________________________________________________________________
58 ___________________________________________________________________M210925EN-B
Example (ASCII and NMEA 0183, device address 0):
0XU<cr><lf>
0XU,A=0,M=P,T=0,C=2,B=19200,D=8,P=N,S=1,L=25,
N=WMT50,V=1.00<cr><lf>
Example (SDI-12, device address 0):
0XXU!
0XXU,A=0,M=S,T=0,C=1,B=1200,D=7,P=E,S=1,L=25,
N=WMT50,V=1.00<cr><lf>
NOTE
There are two different SDI-12 modes available for providing all the
functionality of the SDI-12 v1.3 standard.
The lowest power consumption is achieved with the Native SDI-12
mode (
aXU,M=S
), as it makes measurements and outputs data only on
request.
In the continuous SDI-12 mode (
aXU,M=R
) internal measurements
are made at a user-configurable update interval, see
Chapter 8, Sensor
and Data Message Settings, on page 95
. The data is outputted on
request.
Содержание WINDCAP WMT52
Страница 1: ...USER S GUIDE Vaisala WINDCAP Ultrasonic Wind Sensor WMT52 M210925EN B ...
Страница 143: ...www vaisala com M210925EN ...