5. Configure the relay settings:
a. In
Relay off/on
, set the relay off to edit settings.
b. In
Source
, select the source for the measurement parameter that controls the relay.
c. In
Parameter
, select the measurement parameter that controls the relay.
d. In
Activation
, select whether the relay activates above or below the activation/
deactivation limit.
e. In
Limit
, define the limit which the measured parameter value must reach for the relay
to activate/deactivate.
f. In
Hysteresis
, define a buffer value for relay deactivation. With hysteresis, an
activated relay switches off only when the measured value crosses the relay
activation/deactivation limit and the additional buffer value.
g. Set the relay on.
h. Select
Apply
.
6. Repeat
for all the relays you want to use.
More information
‣
Relay configuration example (page 54)
‣
Relay wiring and relay activation mode (page 54)
‣
7.4 Enabling Modbus TCP/IP in web interface
You need
Administrator
user rights for this task.
1. Connect to the web interface.
2. Log in to the web interface as an administrator user.
3. Select
Transmitter > Network
.
4. Check that the network settings are set correctly.
5. Select
Outputs > Modbus TCP/IP
.
6. In
Modbus off/on
, set Modbus on.
7. Select
Apply
.
More information
‣
Indigo 520 User Guide
M212287EN-A
60
Содержание Indigo 500 Series
Страница 1: ...M212287EN A User Guide Indigo 500 Series Transmitters Indigo 520...
Страница 5: ...Maintenance and calibration 77 Warranty 77 Technical support 77 Recycling 77 Table of contents 3...
Страница 8: ...Indigo 520 User Guide M212287EN A 6...
Страница 80: ......
Страница 81: ......
Страница 82: ...www vaisala com...