6.4.3 Relay hysteresis
If the measurement you are using to control the relay is likely to move back and forth close to
the activation setpoint, you can set a hysteresis that prevents the relay switching on and off
too frequently.
When hysteresis is used, the relay activates at the defined limit, but does not switch off
immediately when the measurement moves back to the other side of the activation limit.
Instead, with hysteresis, the relay remains active until the measurement crosses the relay
activation/deactivation limit and the additional buffer value.
1
3
2
Figure 24 Behavior of relay that activates
above limit, with hysteresis
1
Measurement goes above the relay
activation limit (solid line —) and the
relay activates.
2
Measurement falls below the activation
limit, but stays above the hysteresis
limit (dashed line - - -). The relay
remains active.
3
Measurement falls below the hysteresis
limit and the relay switches off.
6.5 Enabling Modbus TCP/IP on touchscreen
1. Select
Menu > Transmitter > Network
.
2. Make sure that
Network off/on
is set on, and that the network settings are set correctly.
3. Select
Menu > Outputs > Modbus TCP/IP
.
4. In
Modbus off/on
, set Modbus on.
More information
‣
Chapter 6 – Configuring transmitter using touchscreen display
55
Содержание Indigo 500 Series
Страница 1: ...M212287EN A User Guide Indigo 500 Series Transmitters Indigo 520...
Страница 5: ...Maintenance and calibration 77 Warranty 77 Technical support 77 Recycling 77 Table of contents 3...
Страница 8: ...Indigo 520 User Guide M212287EN A 6...
Страница 80: ......
Страница 81: ......
Страница 82: ...www vaisala com...