6.4.1 Relay configuration example
This example shows how to configure a relay to activate when relative humidity
measurement from Probe 1 goes above 90 %RH, and to switch off only when the
measurement falls below 85 %RH (hysteresis). To configure the relay, use the following
values:
•
Relay off/on
: Set relay off to edit settings.
•
Parameter
: Relative humidity
•
Activation
: Active above limit
•
Limit
: 90
•
Hysteresis
: 5
•
Relay off/on
: Set relay on to activate settings.
6.4.2 Relay wiring and relay activation mode
The physical relay opens and closes the circuit depending both on the relay wiring
and the relay activation mode.
Table 8 Relay wiring: Normally open (NO)
Relay activation mode
Measurement above/below
limit
Relay opened/closed
Relay active above limit
Above = Relay active
Closed
Below = Relay inactive
Open
Relay active below limit
Above = Relay inactive
Open
Below = Relay active
Closed
Table 9 Relay wiring: Normally closed (NC)
Relay activation mode
Measurement above/below
limit
Relay opened/closed
Relay active above limit
Above = Relay active
Open
Below = Relay inactive
Closed
Relay active below limit
Above = Relay inactive
Closed
Below = Relay active
Open
Indigo 520 User Guide
M212287EN-A
54
Содержание Indigo 500 Series
Страница 1: ...M212287EN A User Guide Indigo 500 Series Transmitters Indigo 520...
Страница 5: ...Maintenance and calibration 77 Warranty 77 Technical support 77 Recycling 77 Table of contents 3...
Страница 8: ...Indigo 520 User Guide M212287EN A 6...
Страница 80: ......
Страница 81: ......
Страница 82: ...www vaisala com...