Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data
Format
Notes
515
0203
hex
Error code
32-bit
integer
0 = No errors
Table 28 Error Codes on Modbus Interface
Error Code Register
Value
Corresponding Error
0
No errors.
1
Temperature measurement error. [44]
2
Humidity measurement error. [45]
64
Device settings corrupted. [50]
128
Additional configuration settings corrupted. [51]
256
Sensor coefficients corrupted. [52]
512
Main configuration settings corrupted. [53]
2048
Supply voltage out of range. [55]
65536
Non-volatile memory read/write failure. [57]
131072
Firmware checksum mismatch. [49]
If several errors are active at the same time, the Modbus Error Code register contains the sum
of currently active error codes.
Refer to
Error Messages in Insight Software (page 67)
for more information about the error
states.
A.4.3 Configuration Registers
Table 29 Modbus Configuration Data Registers (Writable)
Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data
Format
Unit / Valid
Range
Settings
769
0300
hex
Pressure, power-up default
value
32-bit float
bar (absolute)
0.001 ... 50
771
0302
hex
Pressure
32-bit float
bar (absolute)
0.001 … 50
DMT143 User Guide
M211435EN-J
78
Содержание DRYCAP DMT143