Operating Manual geoTHERM VWS/VWW 0020051578_01
5.12 Troubleshooting
and
diagnosis
5.12.1 Error messages on the controller
Error messages appear roughly 20 seconds after the
error has occurred in the display and are written in the
error memory of the controller if the error persists for
roughly 3 minutes. The engineer can then call up the
error message from the memory at a later date.
Error History
I1
Fault number
>1
Fault code
41
16.02.08 07:18
Error CH circuit
Sensor T3 heat source
Fig. 5.7 Error message in the error memory Menu I1
The geoTHERM control system has various malfunction
types:
– Malfunction of
components
which are connected via
eBUS
.
–
Temporary shutdown
The heat pump remains in operation. The error is dis-
played and disappears independently when the cause
of the fault is removed.
–
Fault-induced shutdown
The heat pump is shut down. It can only be restarted
after the cause of the fault has been removed by the
expert technician and the error reset.
– Moreover,
other errors/malfunctions
can occur on
the unit or system.
a
Caution!
Heat pump malfunction!
Immediately notify your expert techni-
cian if error messages appear on the dis-
play on the operating panel which are
not listed in tables 5.4 to 5.7.
Do not attempt to remove the source of
the malfunction yourself.
h
Note!
Not all of the following listed malfunc-
tions have to be dealt with by an expert
technician.
If you are unsure whether you can reme-
dy the fault yourself or not or if the
error occurs repeatedly contact your
expert technician or Vaillant customer
service.
5.12.2 Activating emergency mode
Depending on the type of malfunction the expert techni-
cian can set the heat pump to continue operation in
emergency mode (via an integrated electric auxiliary
heating) until the cause of the error is remedied, and ei-
ther for heating operation (display "heating priority"),
for hot water operation (display "hot water priority") or
for both (display "heating priority/hot water priority"),
see the following tables, column "emergency operation".
5.12.3 Errors/malfunctions that you can remedy
Malfunction sign
Possible cause
Solution
Noise in the heating
circuit.
Dirt in the heating
circuit.
Bleeding heating
circuit.
Faulty pump.
Air in the heating
circuit.
Table 5.4 Other malfunctions
5.12.4 Warning messages
The following warning messages do not cause a mal-
function in the operation of the heat pump. The heat
pump is not shut down.
Take note of the error code and text and discuss this
during the next inspection with the expert technician.
Fault code
Error text/description
26
Overheating on compressor pressure side
36
Low brine pressure
Table 5.5 Warning messages, no shutdown
Operation 5
GB
Содержание geoTHERM VWS
Страница 1: ...geoTHERM VWS VWW GB ES ...
Страница 2: ......
Страница 3: ...For the owner Operating manual geoTHERM VWS VWW Heat pump GB ...
Страница 34: ......
Страница 35: ...Para el usuario Instrucciones de uso geoTHERM VWS VWW Bomba de calor ES ...
Страница 66: ......
Страница 67: ......
Страница 68: ...0020051578_01 GBES 032009 Subject to alterations Reservado el derecho a introducir modificaciones ...