![Vaillant flexoTHERM exclusive Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/vaillant/flexotherm-exclusive/flexotherm-exclusive_installation-and-maintenance-instructions-manual_4549438053.webp)
0020213394_05 Installation and maintenance instructions
53
Code
Meaning
Cause
Remedy
F.724
Sensor fault: Fan unit 1 fan inlet
temp.
–
Sensor not connected or sensor
input has short-circuited
–
Check the sensor in the fan unit, and
replace if necessary
–
Replace the cable harness in the fan
unit
F.725
Sensor fault: Fan unit 1 brine flow
temp.
–
Sensor not connected or sensor
input has short-circuited
–
Check the sensor in the fan unit, and
replace if necessary
–
Replace the cable harness in the fan
unit
F.731
High-pressure switch open
–
Refrigerant pressure too high. The
integrated high-pressure switch has
tripped at 46 bar (g) or 47 bar (abs)
–
Insufficient energy output via the
relevant capacitors
–
Purging the building circuit
–
Too low a volume flow as a result
of closing single room controls in an
underfloor heating system
–
Check that the dirt filter that is in
place is permeable
–
Refrigerant flow rate too low (e.g.
electronic expansion valve defective,
4-port valve mechanically blocked,
filter blocked). Inform customer
service.
–
VWL SA (cooling mode): Check the
fan unit for dirt
F.732
Compressor outlet temperature
too high
The compressor outlet temperature is
above 130 °C:
–
Application limits exceeded
–
EEV does not work or does not open
correctly
–
Refrigerant volume too low
–
Check the low-pressure sensor,
compressor inlet sensor and outlet
sensor
–
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
–
Check the refrigerant volume (see
Technical data)
–
Carry out a leak-tightness test
F.733
Evaporation temperature too low
–
No flow rate in the environment
circuit (heating mode)
–
Energy input too low in the environ-
ment circuit (heating mode) or build-
ing circuit (cooling mode)
–
Check the flow rate in the environ-
ment circuit
–
Check the dimensioning of the en-
vironment circuit (heating mode) for
ground/brine and ground water/brine
–
If the building circuit contains ther-
mostatic valves, check that they are
suitable for cooling mode (cooling
mode)
–
VWL SA (heating mode)
–
Check the fan unit for dirt
–
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
–
Check the low-pressure sensor and
compressor inlet sensor
F.735
Evaporation temperature too high
–
Temperature in the environment
circuit (heating mode) or building
circuit (cooling mode) too high for
compressor operation
–
Feed-in of external heat into the
environment circuit
–
Reduce or stop the external heat
that is entering
–
Check the de-icer (does it heat
up even though it is
Off
in the
sensor/actuator test?)
–
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
–
Check the compressor inlet sensor
and low-pressure sensor
F.740
Environment circuit: Inlet temp.
too low
–
Inlet temperature in the environment
circuit too low for the compressor to
start for heating:
–
Air/brine: Environment circuit inlet
temperature < -28 °C
–
Ground/brine: Environment circuit
inlet temperature < -7 °C
–
Ground water/brine: Ground water
inlet temperature < 2 °C
–
Check the dimensioning of the envir-
onment circuit
–
Check the sensors